Inspections for the day of: Wednesday, July 7, 2010.
Number of inspections: 17
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00262 INSP-Sprinkler Rough-in7/7/20107/7/20107/7/2010 4:21:13 PMPPASS
The underground stub-in is ok for cover.
FIR10-00288 INSP-Final Inspection7/6/20107/7/20107/7/2010 4:19:24 PMPFAIL
The netcon was a 5. The alarm and trouble signals tested ok. No supervisory signal was being separately transmitted but was instead transmitting out under the trouble contacts. Per Sean Stone, at SimplexGrinnell, this Autocall panel is capable of providing an individual supervisory signal with an additional relay. Since this panel is capable of this a separate supervisory signal is required.
BLD09-02047 FIRE-Final Inspection7/7/20107/7/20107/7/2010 2:36:56 PMPPASS
Life safety passed.
FIR10-00082 INSP-Final Inspection7/7/20107/7/20107/7/2010 2:36:10 PMPPASS
Permit finaled
FIR09-00107 FIR-Aging Inspection7/7/20107/7/20107/7/2010 10:03:04 AM NR
Per Bill the AES inspection scheduling is being addressed.
FIR09-00083 FIR-Aging Inspection7/7/20107/7/20107/7/2010 10:02:34 AM NR
Per Bill the AES inspection scheduling is being addressed.
FIR09-00095 FIR-Aging Inspection7/7/20107/7/20107/7/2010 10:02:09 AM NR
Per Bill the AES inspection scheduling is being addressed.
FIR09-00077 FIR-Aging Inspection7/7/20107/7/20107/7/2010 10:01:39 AM NR
Per Bill the AES inspection scheduling is being addressed.
BLD10-00383 FIRE-Final Inspection7/6/20107/7/20107/7/2010 10:00:17 AMAPASS
Life safety passed. I spoke to the store manager about relocating product that had been set up in front of the west most exit doors.
BLD10-00661 FIRE-Final Inspection7/7/20107/7/20107/7/2010 9:59:17 AMPPASS
Life safety passed. The emergency lights have been repaired and the door mags have been addressed under a separate permit.
FIR06-00254 INSP-Conference7/7/20107/7/20107/7/2010 9:58:20 AMPDONE
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR05-00109 INSP-Conference7/7/20107/7/20107/7/2010 9:58:03 AMPDONE
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR04-00634 INSP-Conference7/7/20107/7/20107/7/2010 9:57:47 AMPDONE
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR00-00269 INSP-Conference7/7/20107/7/20107/7/2010 9:57:31 AMPDONE
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR02-00268 INSP-Conference7/7/20107/7/20107/7/2010 9:57:12 AMPDONE
I went over the outstanding issues as per the permit history with Keith at ADT.
FIR10-00308 INSP-Final Inspection7/6/20107/7/20107/7/2010 9:56:17 AMAPASS
Permit finaled
FIR05-00109 INSP-Conference7/2/20107/7/2010 A 
Follow up conference with Mike; ###-####