ELE12-01179
| ELE-Aging Inspection | 7/7/2014 | 7/7/2014 | 7/7/2014 3:45:24 PM | | DONE |
|
|
Still under construction
|
GCE14-00103
| GCE-Rough-In Permanent Service | 7/7/2014 | 7/7/2014 | 7/7/2014 3:28:09 PM | P | FAIL |
|
|
Daniel ###-#### 110.27(A)- Panel board live parts shall be guarded against accidental contact. 300.4- NM cable shall be protected from physical damage where bored hole thru framing member does not maintain 1 1/4" from framing surface. Left of fire place, and where ran thru lower plate to crawl through shallow hole. 314.25- All boxes shall have covers. Can by utility. 334.30 NM cable shall be supported with in 4 1/2' of upper plate. 4 way by court yard. Oven NM cable shall be secured with in 12" of box.
|
GCE14-00101
| GCE-Temporary Service | 7/7/2014 | 7/7/2014 | 7/7/2014 2:48:25 PM | P | PASS |
|
|
Rich ###-#### re-inspect t/s u/g n ok
|
ELE14-01819
| Electrical Rough-In | 7/7/2014 | 7/7/2014 | 7/7/2014 2:14:12 PM | P | PASS |
|
|
Contact: Jeremy Thornock. Ufer-ground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Concrete encased electrode and in slab conduits for service rough in ok cover
|
ELE14-01802
| Final | 7/6/2014 | 7/7/2014 | 7/7/2014 1:52:41 PM | P | PASS |
|
|
12 solar panels. AC Micro-inverters only. Knife switch for solar disconnect is in back next to meter. The main panel is inside the house, in laundry room. 20 amp Solar breaker is top of panel, opposite service lugs, and clearly labeled. The panels, inverters and rails are all bonded with #6 ground wire landed in main panel. Give homeowner a heads up for inside access at 208 323 8860. Her name is Candi. Phone #: ###-#### >> Inspection requested via web by Ryan King Final ok
|
ELE14-01809
| Final | 7/5/2014 | 7/7/2014 | 7/7/2014 1:16:10 PM | P | CANC |
|
|
This is the Homeowners number so you can get access call him when you are on the way Jeremy is his name. Any other questions feel free to contact me at ###-#### Brandon Blackham Phone #: ###-#### >> Inspection requested via web by Brandon Blackham Needed permenant service inspection.
|
ELE14-01809
| Permanent Service | 7/7/2014 | 7/7/2014 | 7/7/2014 1:15:49 PM | P | FAIL |
|
|
This is the Homeowners number so you can get access call him when you are on the way Jeremy is his name. Any other questions feel free to contact me at ###-#### Brandon Blackham Phone #: ###-#### >> Inspection requested via web by Brandon Blackham 250.53- Where single pipe or rod is used as grounding electode it shall have supplemental electrode. 210.3- Each branch circuit shall be fused. remove taps off main feeders
|
ELE14-01188
| Final | 7/7/2014 | 7/7/2014 | 7/7/2014 12:28:53 PM | P | FAIL |
|
|
Lock Box-12345 Phone #: ###-#### >> Inspection requested via web by Matthew White 210.52(C)- KItchen counter top spaces 12" or wider shall have receptical outlet installed. 406.12(A)- In dwelling units all areas specified in 210.52 120 volt 15 or 20 amp receptical outlets shall be tamper resistant type. Down bath GFI and back outlet under service. 410.16(A)(1)- Luminaires located in storage space shall have totally enclosed light sources. 314.25- Each box shall have covers
|
ELE14-01810
| Final | 7/6/2014 | 7/7/2014 | 7/7/2014 10:40:41 AM | A | PASS |
|
|
Please call 15 minutes ahead so I can meet you there to open the house. Thanks Eddy at ###-#### Phone #: ###-#### >> Inspection requested via web by Eddy Udry Final ok
|
ELE14-01810
| Electrical Rough-In | 7/7/2014 | 7/7/2014 | 7/7/2014 10:16:36 AM | P | PASS |
|
|
Please call 15 minutes ahead so I can meet you there to open the house. Thanks Eddy at ###-#### Phone #: ###-#### >> Inspection requested via web by Eddy Udry Rough in ok
|
ELE14-01782
| Electrical Rough-In | 7/7/2014 | 7/7/2014 | 7/7/2014 10:15:15 AM | A | PASS |
|
|
ceiling Phone #: ###-#### >> Inspection requested via web by Kevin Burke rough in ok cover
|
ELE14-01478
| Final | 7/2/2014 | 7/7/2014 | 7/7/2014 9:12:49 AM | A | PASS |
|
|
final on kitchen remodel, any questions call Tom @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose Final ok
|
ELE13-00015
| Electrical Rough-In | 7/6/2014 | 7/7/2014 | 7/7/2014 8:49:10 AM | A | PASS |
|
|
Hi Rock, it''s me Rex again. If possible early am inspection would be great. Please call for key location. Rough in of bathroom only. Thanks! Phone #: ###-#### >> Inspection requested via web by Rex Boyles Bath remodel rough in ok cover
|