Inspections for the day of: Monday, July 7, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00196 INSP-Sprinkler Rough-in/Hydro7/3/20147/7/20147/7/2014 3:33:36 PMPCANC
Cancel per Robert
BLD14-01183 FIRE-Final Inspection7/3/20147/7/20147/7/2014 3:33:12 PMPPASS
life safety passed. No duct smoke detectors required due to meeting the exception in IMC for smoke being unable to travel outside of the enclosed area. If walls are built exception may not apply
FIR14-00360 INSP-Final Inspection7/2/20147/7/20147/7/2014 10:49:05 AMAPASS
permit finaled
BLD13-03201 FIRE-Final Inspection7/3/20147/7/20147/7/2014 10:30:10 AMAPASS
life safety passed
FIR14-00196 INSP-Sprinkler Rough-in/Hydro7/2/20147/7/20147/7/2014 9:57:31 AMAFAIL
Resubmitt plans showing all of the additional fittings and routing changes. Provide steel riser. Provide pipe sizing as per the plans. Provide sprinkler coverage above the fire place. Provide tenting as discussed. Provide enclosure for piping above garage as per approved plans. Do not cover piping.