ELE15-01902
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 3:33:18 PM | P | PASS |
|
|
late pm Scott Phone #: ###-#### All electrical surface mounted. No card posted. Final ok
|
ELE15-02069
| Conference | 7/7/2015 | 7/7/2015 | 7/7/2015 2:56:29 PM | P | DONE |
|
|
This is a conference to meet at the Starbucks jobsite at Boise Town Square Mall to discuss the proximity of the new sink to the existing electrical panels. Please contact Jay Sprik, ###-####, to determine what time to meet. Phone #: ###-#### Inspection requested via web by Richard Montgomery Discussed minimum distance from a panel to a sink. Boise City Ordinance Section 4-05 31-SPECIAL CODE REQUIREMENTS In addition to the provisions specified in this Section, the Director of the Planning & Development Services Department may require other safeguards based on special conditions that may be present in a particular installation. These safeguards include but are not limited to the following: A. Disconnect and Panel Locations. Main Circuit disconnecting switches and/or distribution panels shall not be installed in a bathroom, shower room, toilet room or next to a washbasin, laundry tub, janitor's tub or other location thought unsafe by the inspector. Minimum distance of 3' waters edge to bussing.
|
ELE15-02068
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 2:18:40 PM | P | FAIL |
|
|
Call 30 mins before // Tom Phone #: ###-#### 210.8(B)(7)- Receptacle outlets located in locker rooms with shower facilities shall have GFCI protection
|
ELE15-02067
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 2:14:05 PM | P | PASS |
|
|
Call 30 mins before // Tom Phone #: ###-#### Listing, and labelling, confirmed. Final ok
|
ELE15-02037
| Permanent Service | 7/7/2015 | 7/7/2015 | 7/7/2015 1:25:28 PM | P | PASS |
|
|
ok to cover // Dan Phone #: ###-#### Under ground conduit not connected to conduit below meter base. p/s u/g n ok
|
ELE15-02037
| Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 1:24:08 PM | P | PASS |
|
|
ok to cover // Dan Phone #: ###-#### Rough in ok cover
|
ELE15-02064
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 12:37:55 PM | P | FAIL |
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender See rough in
|
ELE15-02063
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 12:37:33 PM | P | FAIL |
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender See rough in
|
ELE15-02063
| Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 12:37:02 PM | P | FAIL |
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender 250.53(A)(3)- Water piping system used for grounding electrode shall have supplemental rod. 334.12(B)(4)- NM cable shall not be install in a damp or wet location. Whip from disc to AC. 200.7(C)- If white conductor is used for other than grounded conductor it shall be re-identified other than white. Verbal with contact
|
ELE15-02064
| Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 12:35:06 PM | P | FAIL |
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender 110.14- Dissimilar metals shall not be in physical contact with each other in connnector. 422.30- A disconnecting means shall be provided for furnace with in sight of unit. Verbal with contact.
|
ELE15-01698
| Final | 7/6/2015 | 7/7/2015 | 7/7/2015 11:14:28 AM | A | CANC |
|
|
Floor heat only please.... Inspection requested via web by Paula Gratiot needed rough in inspection
|
ELE15-01698
| Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 11:13:37 AM | P | PASS |
|
|
Floor heat only please.... Inspection requested via web by Paula Gratiot floor heat rough in ok cover
|
ELE15-01990
| Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/7/2015 10:50:18 AM | A | PASS |
|
|
Matt Phone #: ###-#### Addition above garage rough in ok cover
|
ELE15-01292
| Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/7/2015 10:32:52 AM | A | FAIL |
|
|
would like call ahead; Jason Phone #: ###-#### Owner did not call for a conference. 210.12(C)(3)-All 120 volt receptacle outlets located in bath area shall be on a dedicated 20 amp circuit and shall have no other outlets. 240.3(C)- 20 amp circuits shall be completed with 12 ga. wiring. 300.4- NM cable shall be secured at least 1 1/4" from framing surface. 314.16- Box fill shall not exceed rating on box. BCC- Roof shall have moisture barrier installed. NM cable not rated for exposure to weather. BCC- Make up shall be completed and boxes shall be installed at all light locations.
|
ELE15-01922
| Final | 7/6/2015 | 7/7/2015 | 7/7/2015 9:45:11 AM | A | PASS |
|
|
Bob Thomas Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE15-01641
| Final | 7/6/2015 | 7/7/2015 | 7/7/2015 9:20:07 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Needed temp service inspection
|
ELE15-01641
| Temporary Service | 7/7/2015 | 7/7/2015 | 7/7/2015 9:19:54 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt t/s u/g n ok
|