ELE12-01179
| ELE-Aging Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 4:15:48 PM | | DONE |
|
|
called office but in fax machine mode
|
ELE13-00701
| ELE-Aging Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 4:13:04 PM | | DONE |
|
|
left message
|
ELE12-01429
| ELE-Aging Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 4:10:16 PM | | DONE |
|
|
left another message
|
ELE12-02459
| ELE-Aging Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 4:07:32 PM | | DONE |
|
|
left another message for Dave
|
ELE13-00718
| ELE-Aging Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 3:59:38 PM | | DONE |
|
|
left message for Shawn
|
ELE15-01145
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 3:29:14 PM | P | FAIL |
|
|
The access code is 6175, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 210.12- AFCI protection required in all bdrms. (DNST. bdrm)
|
ELE15-01857
| Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 2:47:49 PM | P | PASS |
|
|
Basement and Kitchen is ready for rough-in cover... Phone #: ###-#### Inspection requested via web by JOHN MCCURDY bsmt and kitchen ok to cover
|
ELE13-02281
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 2:20:28 PM | P | PASS |
|
|
Call 20 mins before // Patrick Phone #: ###-#### final ok on service upgrade
|
ELE14-03246
| Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/7/2015 2:06:45 PM | P | CANC |
|
|
Levi. Tower #4 Floor #2. Phone #: ###-#### Inspection requested via web by Sean DeLacy not ready
|
ELE14-03334
| Final | 7/7/2015 | 7/7/2015 | 7/7/2015 2:05:41 PM | A | PART |
|
|
Contact: Jeremy Thornock Phone #: ###-#### Inspection requested via web by Deb Gooden partial final ok 3rd flr rms west wing and corridors
|
ELE14-03246
| Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/7/2015 12:03:40 PM | A | NR |
|
|
Levi. Tower #2 5th Floor Final. Phone #: ###-#### Inspection requested via web by Sean DeLacy partial final/not 100% ready
|
ELE13-01291
| Final | 7/2/2015 | 7/7/2015 | 7/7/2015 10:35:25 AM | A | FAIL |
|
|
Contact Brandon Robinson for room by room final inspections starting on level 1. Phone #: ###-#### Inspection requested via web by Tom Betty 422.31 and 422.32-disconnect and lockoff required for hand dryers, 210.8(B)-GFCI protection required in other than dwellings kitchens for all 125 volt 20amp receptacles, 422.52-all drinking fountains shall have GFCI protection. 406.8(B)-all receptacles in wet locations shall be listed "weather resistant" type. Please have listings for lumiaires available for inspections.
|
ELE15-02131
| Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 12:00:00 AM | A | PASS |
|
|
5th floor drop ceilings. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i ok rm. soffits in 515,518 thru 524, 526 thru 528
|
ELE14-03246
| Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/6/2015 8:59:13 AM | A | CANC |
|
|
Levi. Tower 4 soffit cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|