BLD15-00697
| FIRE-Final Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 2:59:33 PM | P | FAIL |
|
|
All items have been addressed except the door mags at the main entrance. Per my conversation with Carl in plan review the door mags need to be code compliant and tested.
|
BLD15-02152
| FIRE-Final Inspection | 7/6/2015 | 7/7/2015 | 7/7/2015 2:12:30 PM | P | PASS |
|
|
Life safety passed
|
BLD15-01747
| FIRE-Final Inspection | 7/6/2015 | 7/7/2015 | 7/7/2015 1:30:16 PM | A | PASS |
|
|
life safety passed
|
BLD15-00592
| FIRE-Final Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 1:11:43 PM | P | PASS |
|
|
Life safety passed
|
BLD15-02238
| FIRE-Final Inspection | 7/6/2015 | 7/7/2015 | 7/7/2015 12:47:01 PM | A | FAIL |
|
|
Provide correct suite number, provide sticker remove thumbturn and provide single action hardware at the main/front exit, provide fire extinguisher as discussed.
|
BLD15-00199
| FIRE-Final Inspection | 7/7/2015 | 7/7/2015 | 7/7/2015 10:26:15 AM | P | PART |
|
|
Rooms 206, 207 and the associated offices life safety is passed. This is a phased project.
|
BLD15-02007
| FIRE-Final Inspection | 7/6/2015 | 7/7/2015 | 7/7/2015 10:24:01 AM | A | FAIL |
|
|
No city approved plans on site. I met the broker and went over general life safety requirements. I noted missing fire extinguishers, multiple keyed dead bolts on the four store front exit doors, existing round knobs that may need updated and new round knobs that I know need to be updated, two new exit signs have been installed but no emergency lights, need verification that the new hvac units do not require duct detectors. Also the main exit door has manual flush bolts installed on the inactive leaf and there is a large overhead roll down door that can be pulled down infront of the main exit door.
|
BLD15-01408
| FIRE-Final Inspection | 7/6/2015 | 7/7/2015 | 7/7/2015 9:17:29 AM | A | PASS |
|
|
Life safety passed
|
FIR15-00436
| INSP-Final Inspection | 7/6/2015 | 7/7/2015 | 7/7/2015 8:10:15 AM | A | PART |
|
|
The fire alarm in Room 206, 207 and associated Offices is complete. The fire/smoke damper has been repaired.
|
FIR15-00436
| INSP-Sprinkler Rough-in/Hydro | 7/6/2015 | 7/7/2015 | 7/6/2015 11:24:23 AM | A | CANC |
|
|
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Inspection cancelled via mobile web on Monday, July 06, 2015.
|