Inspections for the day of: Tuesday, July 7, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00697 FIRE-Final Inspection7/7/20157/7/20157/7/2015 2:59:33 PMPFAIL
All items have been addressed except the door mags at the main entrance. Per my conversation with Carl in plan review the door mags need to be code compliant and tested.
BLD15-02152 FIRE-Final Inspection7/6/20157/7/20157/7/2015 2:12:30 PMPPASS
Life safety passed
BLD15-01747 FIRE-Final Inspection7/6/20157/7/20157/7/2015 1:30:16 PMAPASS
life safety passed
BLD15-00592 FIRE-Final Inspection7/7/20157/7/20157/7/2015 1:11:43 PMPPASS
Life safety passed
BLD15-02238 FIRE-Final Inspection7/6/20157/7/20157/7/2015 12:47:01 PMAFAIL
Provide correct suite number, provide sticker remove thumbturn and provide single action hardware at the main/front exit, provide fire extinguisher as discussed.
BLD15-00199 FIRE-Final Inspection7/7/20157/7/20157/7/2015 10:26:15 AMPPART
Rooms 206, 207 and the associated offices life safety is passed. This is a phased project.
BLD15-02007 FIRE-Final Inspection7/6/20157/7/20157/7/2015 10:24:01 AMAFAIL
No city approved plans on site. I met the broker and went over general life safety requirements. I noted missing fire extinguishers, multiple keyed dead bolts on the four store front exit doors, existing round knobs that may need updated and new round knobs that I know need to be updated, two new exit signs have been installed but no emergency lights, need verification that the new hvac units do not require duct detectors. Also the main exit door has manual flush bolts installed on the inactive leaf and there is a large overhead roll down door that can be pulled down infront of the main exit door.
BLD15-01408 FIRE-Final Inspection7/6/20157/7/20157/7/2015 9:17:29 AMAPASS
Life safety passed
FIR15-00436 INSP-Final Inspection7/6/20157/7/20157/7/2015 8:10:15 AMAPART
The fire alarm in Room 206, 207 and associated Offices is complete. The fire/smoke damper has been repaired.
FIR15-00436 INSP-Sprinkler Rough-in/Hydro7/6/20157/7/20157/6/2015 11:24:23 AMACANC
As early as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Inspection cancelled via mobile web on Monday, July 06, 2015.