Inspections for the day of: Tuesday, July 7, 2015.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00167 INSP-Final Inspection7/2/20157/7/20157/7/2015 1:56:20 PMPPASS
Flush test of the FS U/G supply line from the 11th street connection to the pump header (pump was bypassed). Flushed clear after 2 attempts.
OK to connect this supply line to the pump suction feed main.
FIR13-00167 INSP-Sprinkler Rough-in/Hydro7/7/20157/7/20157/7/2015 11:39:16 AMPPASS
Completion of 24 hour air test of four (4) dry pipe valves located in the U/G parking garage. All PASSED.
FIR14-00815 INSP-Sprinkler Rough-in7/6/20157/7/20157/7/2015 10:35:07 AMAPART
Rough to cover inspection for the corridors on floors 2 and 3, in section 3 of the building.
OK to cover pipe.