ELE13-02196
| ELE-Aging Inspection | 7/7/2016 | 7/7/2016 | 7/8/2016 6:28:25 AM | | CANC |
|
|
|
ELE15-02740
| Electrical Rough-In | 7/7/2016 | 7/7/2016 | 7/7/2016 2:24:28 PM | P | PASS |
|
|
Sath Phone #: ###-#### Potting rough in ok cover
|
ELE16-02146
| Electrical Rough-In | 7/7/2016 | 7/7/2016 | 7/7/2016 1:59:16 PM | P | PASS |
|
|
JR Phone #: ###-#### Walls and ceiling rough in ok cover
|
ELE16-01874
| Electrical Rough-In | 7/7/2016 | 7/7/2016 | 7/7/2016 1:29:24 PM | P | CANC |
|
|
Underground for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean Needed final inspection
|
ELE16-01874
| Final | 7/7/2016 | 7/7/2016 | 7/7/2016 1:29:08 PM | P | PASS |
|
|
Underground for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean Final ok
|
ELE15-00495
| Electrical Rough-In | 7/7/2016 | 7/7/2016 | 7/7/2016 11:34:00 AM | A | PASS |
|
|
Ceiling inspection elevator lobbies. Reinspect fire Corridor first floor. Contact is Eric Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves 1st floor corridor, Elevator lobbies 1 thru 6 ceiling as noted in book rough in ok cover
|
ELE16-01971
| Electrical Rough-In | 7/6/2016 | 7/7/2016 | 7/7/2016 10:41:07 AM | A | PASS |
|
|
Panel and inverter listing inspection. Phone #: ###-#### Inspection requested via web by Ryan King Enphase arrays listing confirmed rough in ok
|
ELE16-01971
| Final | 7/7/2016 | 7/7/2016 | 7/7/2016 10:34:04 AM | P | PASS |
|
|
Panel and inverter listing inspection. Phone #: ###-#### Inspection requested via web by Ryan King ' Final ok
|
ELE16-02104
| Temporary Service | 7/6/2016 | 7/7/2016 | 7/7/2016 10:02:48 AM | A | FAIL |
|
|
Temp Power pole Phone #: ###-#### Inspection requested via web by Cathy Duchek 400.5- Max overcurrent device for #8 3 conductor flexible cord 35 amps 50 amp installed. 590.6(B)- All temp power other than 120 volt receptacles shall have GFCI protection. Verbal with contact,
|
ELE16-01138
| Final | 7/6/2016 | 7/7/2016 | 7/7/2016 9:34:50 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson Final ok
|
ELE16-02132
| Temporary Service | 7/6/2016 | 7/7/2016 | 7/7/2016 9:15:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman t/s u/g n ok
|