Inspections for the day of: Thursday, July 7, 2016.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00052 INSP-Supply line flush7/6/20167/7/20167/8/2016 6:38:34 AMPCANC
Rescheduled for tomorrow morning
BLD15-02821 FIRE-Final Inspection7/7/20167/7/20167/7/2016 2:45:20 PMPFAIL
Per my interpretation of the drawings/scope of work atleast two exit signs are required, two fire extinguishers, new emergency lighting at the plane end of the tunnel and testing of the new lighting at the concourse end of the tunnel. Contractor is going to contact my supervisor to see if the intent is for the entire tunnel or just their new section.
FIR16-00131 INSP-Final Inspection7/5/20167/7/20167/7/2016 2:42:40 PMPPART
Todays inspection was just for the jet-X 2% Foam Test. The system was activated by the smoke detectors and from time of smoke detector activation to discharge of foam was 5 seconds. The entire floor area to the walls and to a minimum depth of 2'-6" was achieved with-in 60 seconds. TVFP will provide documentation for the concentration, water flow and quantity of foam used. Also they need to provide the fire pump certification documents prior to a final sign off.
BLD15-01869 FIRE-Conference7/6/20167/7/20167/7/2016 10:48:28 AMADONE
Pressure was 64psi this morning
FIR15-00822 INSP-Conference7/6/20167/7/20167/7/2016 10:48:08 AMADONE
Pressure was 64psi this morning