Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-03717 FIRE-Final Inspection7/6/20177/7/20177/7/2017 12:13:13 PMPPART
Temporary CofO ok for employees only per discussion with building inspector. Two items to be corrected:
- Main Entrance (parking lot side) exterior egress light to be repaired.
-Second exit door to have thumb turn deadbolt removed and shall have panic hardware per code and plan sheet A8.01. (Discussed that paddle hardware device is ok).
FIR17-00170 INSP-Final Inspection7/6/20177/7/20177/7/2017 12:01:06 PMAPASS
Systems acceptance test completed satisfactory. Scope of Work Complete, Permit Finaled.
BLD17-01120 FIRE-Final Inspection7/6/20177/7/20177/7/2017 9:22:36 AMACANC
Cancelled and pushed to when alarm final called in again.
FIR17-00355 INSP-Final Inspection7/6/20177/7/20177/7/2017 9:21:36 AMAFAIL
Device required in training room. It was shown as an office on the plans but systems furniture in place is for conference/training. Alarm was tested and all other devices are good.