FIR20-00262
| INSP-Final Inspection | 7/1/2020 | 7/7/2020 | 7/7/2020 11:48:31 AM | A | PASS |
|
|
Previously noted synch issues on notification appliances have been resolved. All notification appliances were tested.
Please call 20-30 minutes prior to inspection. You will be meeting technician Jason Petty on site. Phone #: ###-#### Inspection requested via web by jason petty
|
FIR20-00232
| INSP-Final Inspection | 6/30/2020 | 7/7/2020 | 7/7/2020 11:41:51 AM | A | FAIL |
|
|
Smoke detectors in great room need to be within 36" of peak of ceiling. CO detector required in mechanical room above furnace. Additional smoke and smoke/CO detectors that are located in bedrooms, halls and other rooms are not interconnected to the FA system and will not activate occupant notification. No testing completed.
Please call 20-30 minutes prior to inspection. You will be meeting technician Justin Volquardsen on site. Phone #: ###-#### Inspection requested via web by jason petty
|