ELE02-01458
| Electrical Rough-In | 7/7/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | A | PASS |
|
|
tom ceiling cover; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok conference rms a&b 7/8/2003 1:38:19 PM
|
ELE02-02684
| Electrical Rough-In | 7/7/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | A | PASS |
|
|
ernest; Phone #: ###-#### Internet Inspection Request from: Barbara Moore r/i ok rm 515 7/8/2003 2:10:30 PM
|
ELE03-01564
| Final | 7/8/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | PASS |
|
|
roni; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 7/8/2003 3:31:39 PM
|
ELE03-02012
| Electrical Rough-In | 7/8/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | FAIL |
|
|
after 2 please ###-#### gordon cor. and do not cover posted met with contractor 210.52(B&C) family rm and liviing rm on small appliance branch circuit, 250.148 tie all grds together in boxes 334.112 use type NM-B cable he use some type MN old stuff not 90 degree C rated 7/8/2003 4:34:01 PM
|
ELE03-01035
| Final | 7/7/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/7/2003 at 8:26:09 AM. Contact: ###-####. final ok control wiring 7/8/2003 2:52:51 PM
|