MIS03-00130
| FIR-Final | 7/2/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | A | FAIL |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need exit signs in basement as two exits required; need sprinkler head under stairs or seal off; need emergency lights for main floor; need penetration firestopped in corridor 7/8/2003 10:52:14 AM
|
BLD03-01106
| FIRE-Final Inspection | 7/2/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | A | FAIL |
|
|
wendy; Phone #: ###-#### Internet Inspection Request from: Annette Moore need approved plans; repair ceiling at new plumbing lines 7/8/2003 10:52:56 AM
|
BLD03-00416
| FIRE-Final Inspection | 7/8/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | A | PASS |
|
|
Cathy has the sign off card - please let her know when approved! okay for occupancy 7/8/2003 9:39:29 AM
|
FIR03-00346
| INSP-Conference | 7/8/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/8/2003 at 8:38:55 AM. Contact: ###-####. not installed per plans and will resubmit with overhead submittals; PIV to be relocated to parking area by vault; UG relocated also due to electrical vault; will need tracer wire and pipe for monitoring PIV 7/8/2003 4:29:08 PM
|
BLD02-00090
| FIRE-Final Inspection | 7/8/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore need closures on doors to corridor; door to lobby locks and is required exit 7/8/2003 4:26:18 PM
|
FIR03-00088
| INSP-Sprinkler Rough-in/Hydro | 7/7/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/7/2003 at 2:34:48 PM. Contact: ###-####. need resubmittals for pipe changes and standpipe changes; need listing for fire stopping standpipe through floor/ceiling assembly; EQ needed; need heat to maintain 40 degrees in north rooms where main enters building through vestibule and bike room 7/8/2003 4:25:01 PM
|
FIR03-00067
| INSP-Sprinkler Rough-in/Hydro | 7/7/2003 | 7/8/2003 | 7/8/2003 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/7/2003 at 2:36:20 PM. Contact: ###-####. resubmittals needed for pipe changes and relocation of inspectors tests; may put systems over 750 gallons; Scheduled by a contractor via Hello! on 7/7/2003 at 2:34:48 PM. Contact: ###-####. need resubmittals for pipe changes and standpipe changes; need listing for fire stopping standpipe through floor/ceiling assembly; EQ needed; need heat to maintain 40 degrees in north rooms where main enters building through vestibule and bike room 7/8/2003 4:25:20 PM
|