Inspections for the day of: Friday, July 8, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00925 Final7/7/20057/8/20057/8/2005 3:53:21 PMPPASS
Phone #: ###-#### Internet Inspection Request from: William Zerfas ok to final
ELE05-01936 Final7/7/20057/8/20057/8/2005 3:52:18 PMAPASS
Scheduled by a contractor via Hello! on 7/7/2005 at 3:28:09 PM. Contact: ###-####. ok to final
ELE05-02430 Temporary Service7/8/20057/8/20057/8/2005 3:11:07 PMPPASS
todd ###-#### called contr to change 50A recpt. t/s u/g n ok
ELE05-02420 Temporary Service7/8/20057/8/20057/8/2005 2:57:14 PMPPASS
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS t/s u/g n ok
ELE05-02269 Electrical Rough-In7/8/20057/8/20057/8/2005 2:23:50 PMPFAIL
lars///entrer from back please; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 250.80 metal enclosures shall be gnded,300.4(A)(1) edge of hole shall be 1 1/4" from edge of framing member, all wiring shall be done (BCC), called contr, left corr notice
ELE05-02427 Electrical Rough-In7/8/20057/8/20057/8/2005 12:33:32 PMPPASS
Underslab inspection; Phone #: ###-#### Internet Inspection Request from: Nikki Day ok to cover u/g in slab
ELE05-02425 Electrical Rough-In7/8/20057/8/20057/8/2005 12:32:45 PMPNR
Underslab Inspection; Phone #: ###-#### Internet Inspection Request from: Nikki Day neede to recall
ELE04-03723 Final7/7/20057/8/20057/8/2005 11:57:41 AMAFAIL
Scheduled by a contractor via Hello! on 7/7/2005 at 3:17:37 PM. told contr, left corr notice, 314.21 drywall shall be repaired,314.23 boxes shall be securely supported,314.25 boxes shall have covers, 408.7 unused openings shall be closed, 408.4 circuit directory shall be clear, 404.9(A) faceplates shall be provided, 110.3(A)(8)gfci shall operate correctly,110.2 equipment shall be installed
ELE05-01684 Final7/7/20057/8/20057/8/2005 9:31:41 AMAPART
lee; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr to ground chlorine generator.
ELE05-02393 Permanent Service7/6/20057/8/20057/8/2005 9:21:36 AMAFAIL
kelly felin- ###-#### nec 550.11(D) nameplate shall be provided to show feeder voltage and amperage, called left message and correction notice
ELE05-02161 Conference7/7/20057/8/20057/8/2005 8:38:29 AMANH
You will meet with Sean the journeyman electrician on the job. His # is ###-####; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called elect at job site, he was on other job doing service change, and said we need to do Monday. Isaid to recall.
ELE05-02357 Electrical Rough-In7/7/20057/8/20057/8/2005 8:28:45 AMAPASS
One time inspection for extending electrical and adding fixtures , ready for final Thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
ELE05-02416 Rough-In Permanent Service7/7/20057/8/20057/8/2005 8:17:41 AMAPASS
tom ###-#### called contr to provide gec abrasion protection. ric ok ,p/s u/g n ok
ELE05-02408 Final7/7/20057/8/20057/8/2005 8:00:23 AMACANC
clay ###-#### see ric
ELE05-02408 Electrical Rough-In7/8/20057/8/20057/8/2005 12:00:00 AMAPASS
clay ###-#### ric ok
ELE05-02418 Rough-In Permanent Service7/8/20057/8/20057/8/2005 12:00:00 AMPPASS
met contr, told him to add abrasion protection on gnd wire at panel, access plate for gec and 1 recpt in front room. ric ok, p/s u/g n ok