ELE06-04521
| ELE-Aging Inspection | 7/8/2008 | 7/8/2008 | 7/10/2008 9:43:07 AM | | DONE |
|
|
waiting for call, have not seen how floor box installed
|
ELE06-04686
| ELE-Aging Inspection | 7/8/2008 | 7/8/2008 | 7/8/2008 4:07:49 PM | | DONE |
|
|
waitng for contractor to call for inspection
|
ELE08-01852
| Final | 7/8/2008 | 7/8/2008 | 7/8/2008 3:34:17 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-01858
| Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 2:21:27 PM | P | PASS |
|
|
John Phone #: ###-#### p/s o/h rec ok
|
ELE08-01855
| Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 1:48:01 PM | P | FAIL |
|
|
If any questions please call Jeff Creek at ###-####. Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek called left message, left correction notice, NEC 250.52(A)(3) concrete encased electrode shall be min. 20' bare copper not smaller than #4 awg surrounded by at least 2" concrete, 310.11(B) service entrance cable shall bear "sunlight resistant" marking,BCC all u/g shall be inspected before cover
|
ELE08-00662
| Electrical Rough-In | 7/7/2008 | 7/8/2008 | 7/8/2008 12:47:59 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/7/2008 at 8:38:13 PM. Contact: ###-####. concrete encased electrode ok to pour, u/g ok, ric ok shop, called owner, said to call for ri after electrode poured, then can give p/s at that time also
|
ELE08-01029
| Electrical Rough-In | 7/7/2008 | 7/8/2008 | 7/8/2008 11:46:15 AM | A | CANC |
|
|
Danny Phone #: ###-#### contractor calle d to cancel for today
|
ELE08-01852
| Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 10:20:04 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: chris green corrections made, p/s o/h rec ok, no esc this project
|
ELE08-01851
| Final | 7/7/2008 | 7/8/2008 | 7/8/2008 10:16:02 AM | A | PASS |
|
|
clint Phone #: ###-#### ok to final, no esc this project
|
ELE08-01851
| Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 10:07:58 AM | A | PASS |
|
|
clint Phone #: ###-#### p/s u/g rec ok, no esc this project
|
ELE08-00900
| Electrical Rough-In | 7/8/2008 | 7/8/2008 | 7/8/2008 9:49:34 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 7/8/2008 at 6:28:46 AM. Contact: ###-####. ric walls only anop, no esc this project
|
ELE08-01606
| Final | 7/7/2008 | 7/8/2008 | 7/8/2008 8:57:05 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, left correction notice, NEC 358.30(A) shall support emt within 3' of box, 330.30(B) mc shall be secured within 12" of box, 300.11 shall not use grid wires for raceway support, 725.3 shall remove abandoned low voltage wiring,BCC no violations shall be retained, no cables or wiring shall be supported by grid or tiles,no tie-wraps shall be used to support flex conduit, no esc this project
|
ELE08-01852
| Final | 7/7/2008 | 7/8/2008 | 7/8/2008 7:59:23 AM | A | CANC |
|
|
Heather ( office) Phone #: ###-#### wrong type request, see p/s, no esc this project
|
ELE08-01852
| Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 7:58:58 AM | A | FAIL |
|
|
Heather ( office) Phone #: ###-#### called,, left correction notice, NEC 250.26 single electrode shall be augmented by additional electrode if resistance is 25 ohms or less, 312.5 shall provide abrasion protection for all conductors entering enclosure, BCC job id sticker shall be posted, NOTE shall provide access to interior, no esc this project
|