Inspections for the day of: Tuesday, July 8, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04521 ELE-Aging Inspection7/8/20087/8/20087/10/2008 9:43:07 AM DONE
waiting for call, have not seen how floor box installed
ELE06-04686 ELE-Aging Inspection7/8/20087/8/20087/8/2008 4:07:49 PM DONE
waitng for contractor to call for inspection
ELE08-01852 Final7/8/20087/8/20087/8/2008 3:34:17 PMPPASS
ok to final, no esc this project
ELE08-01858 Permanent Service7/8/20087/8/20087/8/2008 2:21:27 PMPPASS
John Phone #: ###-#### p/s o/h rec ok
ELE08-01855 Permanent Service7/8/20087/8/20087/8/2008 1:48:01 PMPFAIL
If any questions please call Jeff Creek at ###-####. Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek called left message, left correction notice, NEC 250.52(A)(3) concrete encased electrode shall be min. 20' bare copper not smaller than #4 awg surrounded by at least 2" concrete, 310.11(B) service entrance cable shall bear "sunlight resistant" marking,BCC all u/g shall be inspected before cover
ELE08-00662 Electrical Rough-In7/7/20087/8/20087/8/2008 12:47:59 PMPPASS
Scheduled by a contractor via Hello! on 7/7/2008 at 8:38:13 PM. Contact: ###-####. concrete encased electrode ok to pour, u/g ok, ric ok shop, called owner, said to call for ri after electrode poured, then can give p/s at that time also
ELE08-01029 Electrical Rough-In7/7/20087/8/20087/8/2008 11:46:15 AMACANC
Danny Phone #: ###-#### contractor calle d to cancel for today
ELE08-01852 Permanent Service7/8/20087/8/20087/8/2008 10:20:04 AMPPASS
Phone #: ###-#### Internet Inspection Request from: chris green corrections made, p/s o/h rec ok, no esc this project
ELE08-01851 Final7/7/20087/8/20087/8/2008 10:16:02 AMAPASS
clint Phone #: ###-#### ok to final, no esc this project
ELE08-01851 Permanent Service7/8/20087/8/20087/8/2008 10:07:58 AMAPASS
clint Phone #: ###-#### p/s u/g rec ok, no esc this project
ELE08-00900 Electrical Rough-In7/8/20087/8/20087/8/2008 9:49:34 AMAPASS
Scheduled by a contractor via Hello! on 7/8/2008 at 6:28:46 AM. Contact: ###-####. ric walls only anop, no esc this project
ELE08-01606 Final7/7/20087/8/20087/8/2008 8:57:05 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, left correction notice, NEC 358.30(A) shall support emt within 3' of box, 330.30(B) mc shall be secured within 12" of box, 300.11 shall not use grid wires for raceway support, 725.3 shall remove abandoned low voltage wiring,BCC no violations shall be retained, no cables or wiring shall be supported by grid or tiles,no tie-wraps shall be used to support flex conduit, no esc this project
ELE08-01852 Final7/7/20087/8/20087/8/2008 7:59:23 AMACANC
Heather ( office) Phone #: ###-#### wrong type request, see p/s, no esc this project
ELE08-01852 Permanent Service7/8/20087/8/20087/8/2008 7:58:58 AMAFAIL
Heather ( office) Phone #: ###-#### called,, left correction notice, NEC 250.26 single electrode shall be augmented by additional electrode if resistance is 25 ohms or less, 312.5 shall provide abrasion protection for all conductors entering enclosure, BCC job id sticker shall be posted, NOTE shall provide access to interior, no esc this project