ELE09-01195
| Temporary Service | 7/8/2009 | 7/8/2009 | 7/8/2009 4:08:19 PM | P | FAIL |
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae met contractor, left correction notice, NEC 110.9 shall provide equipment rated for available fault current, 406.8 15 and 20a receptacles shall be listed weather resistant, no esc this project
|
ELE09-01196
| Temporary Service | 7/8/2009 | 7/8/2009 | 7/8/2009 3:51:10 PM | P | FAIL |
|
|
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae met contractor, told could not hook up trailer with cord since trailer not portable or listed, gave partial correction notice for trailer,Nec 400.5(A) soow cord rated at 45A, 408.4 shall provide circuit directory, 240.81 breaker handles shall be on in up position, 400.8 shall not use so cord for substitution of fixed wiring, left correction notice for temporary pole NEC 406.8 15 and 20a receptacles shall be listed weather resistant, 406.4 receptacle shall have faceplate installed, 110.9 shall provide equipment rated for available fault current, no esc this project
|
ELE09-00622
| Final | 7/8/2009 | 7/8/2009 | 7/8/2009 3:33:17 PM | P | PASS |
|
|
Jarod please call 1/2 hr before going out Phone #: ###-#### ok to final, no esc this project
|
ELE09-01002
| Final | 7/8/2009 | 7/8/2009 | 7/8/2009 3:27:22 PM | P | PASS |
|
|
ok to final ,no esc this project
|
ELE09-01184
| Rough-In Permanent Service | 7/7/2009 | 7/8/2009 | 7/8/2009 3:13:50 PM | P | PASS |
|
|
Inspect new OH service and hot tub. Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ric ok, p/s o/h rec ok, no esc this project
|
ELE09-01150
| Final | 7/8/2009 | 7/8/2009 | 7/8/2009 2:11:34 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 7/8/2009 at 10:49:24 AM. Contact: ###-####. ok to final, signed card, no esc this project
|
ELE09-01166
| Final | 7/3/2009 | 7/8/2009 | 7/8/2009 12:29:38 PM | P | PASS |
|
|
randy ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok to final, no esc this project
|
ELE09-01201
| Electrical Rough-In | 7/8/2009 | 7/8/2009 | 7/8/2009 10:55:16 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Stuart Welton ric ok, no esc this project
|
ELE09-01201
| Final | 7/8/2009 | 7/8/2009 | 7/8/2009 10:54:47 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Stuart Welton ok to final, no esc this project
|
ELE09-00838
| Final | 7/7/2009 | 7/8/2009 | 7/8/2009 10:41:54 AM | A | PASS |
|
|
4272 please do not open man door Phone #: ###-#### Internet Inspection Request from: William Zerfas corrections made, called, ok to final
|
ELE09-01187
| Electrical Rough-In | 7/7/2009 | 7/8/2009 | 7/8/2009 10:09:15 AM | A | PASS |
|
|
Mike Phone #: ###-#### ric ok ,no esc this project
|
ELE09-01200
| Permanent Service | 7/7/2009 | 7/8/2009 | 7/8/2009 9:34:08 AM | A | PASS |
|
|
luz-only speaks spanish Phone #: ###-#### p/s o/h rec ok, no esc this project
|
ELE09-01071
| Final | 7/7/2009 | 7/8/2009 | 7/8/2009 8:54:53 AM | A | PASS |
|
|
george Phone #: ###-#### called, corrections made, ok to final, no esc this project
|
ELE09-01148
| Electrical Rough-In | 7/7/2009 | 7/8/2009 | 7/8/2009 8:24:51 AM | A | PASS |
|
|
Any questions call Bob Parsley ###-####. He is not at this job site but can direct you where to go. Phone #: ###-#### Internet Inspection Request from: Dave Friend called contractor, walls only ok to cover, no esc this project
|
ELE09-01127
| Rough-In Permanent Service | 7/7/2009 | 7/8/2009 | 7/8/2009 7:59:00 AM | A | PASS |
|
|
Tom Phone #: ###-#### corrections made, ri ok, p/s u/g n ok, no esc this project
|