Inspections for the day of: Wednesday, July 8, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00837 INSP-Sprinkler Rough-in/Hydro7/7/20097/8/20097/8/2009 4:59:19 PMAPART
OH Cover - Contact: jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
FIR08-00836 INSP-Sprinkler Rough-in/Hydro7/7/20097/8/20097/8/2009 4:59:08 PMAPART
OH Cover - Contact: Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
FIR08-00835 INSP-Sprinkler Rough-in/Hydro7/7/20097/8/20097/8/2009 4:58:57 PMAPART
OH cover - Contact Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
FIR08-00834 INSP-Sprinkler Rough-in/Hydro7/7/20097/8/20097/8/2009 4:58:43 PMAPART
OH Cover - Contact: Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
FIR09-00033 INSP-Sprinkler Rough-in7/7/20097/8/20097/8/2009 4:57:46 PMAPART
Partial inspection for system #2 completed, noted one leaking coupling, discussed possible obstructions at HVAC units, hangers and pipe sizing appear okay, spacing and head locations at some areas need to be verified at the deck, discussed inspectors test connection orfice sizing at riser manifolds.
BLD09-00301 FIRE-Final Inspection7/7/20097/8/20097/8/2009 4:50:59 PMAPART
See red-lines on plans for racking installation completed and okayed to date. Tenant to provide one additional fire extinguisher and shelf load limit signage at the second level mezzanine as discussed.
FIR09-00052 FIR-Aging Inspection7/8/20097/8/20097/8/2009 12:50:23 PM DONE
Work in progress, also pending site acceptance testing for interconnection to the new fire alarm system.
BLD08-01806 FIRE-Final Inspection7/7/20097/8/20097/8/2009 12:44:49 PMAFAIL
See fire code review notes items #2, 5, and 12 regarding fire dept. access requirements and posting of max. occupant load sign. Also refer to plan sheet a1.11 keynotes #24 and 25 annotated in red for fire lane access to be provided.
BLD09-00591 BLD-Final7/6/20097/8/20097/8/2009 12:39:31 PMAPASS
Fire life safety inspection completed acceptable.