FIR08-00837
| INSP-Sprinkler Rough-in/Hydro | 7/7/2009 | 7/8/2009 | 7/8/2009 4:59:19 PM | A | PART |
|
|
OH Cover - Contact: jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
|
FIR08-00836
| INSP-Sprinkler Rough-in/Hydro | 7/7/2009 | 7/8/2009 | 7/8/2009 4:59:08 PM | A | PART |
|
|
OH Cover - Contact: Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
|
FIR08-00835
| INSP-Sprinkler Rough-in/Hydro | 7/7/2009 | 7/8/2009 | 7/8/2009 4:58:57 PM | A | PART |
|
|
OH cover - Contact Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
|
FIR08-00834
| INSP-Sprinkler Rough-in/Hydro | 7/7/2009 | 7/8/2009 | 7/8/2009 4:58:43 PM | A | PART |
|
|
OH Cover - Contact: Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
|
FIR09-00033
| INSP-Sprinkler Rough-in | 7/7/2009 | 7/8/2009 | 7/8/2009 4:57:46 PM | A | PART |
|
|
Partial inspection for system #2 completed, noted one leaking coupling, discussed possible obstructions at HVAC units, hangers and pipe sizing appear okay, spacing and head locations at some areas need to be verified at the deck, discussed inspectors test connection orfice sizing at riser manifolds.
|
BLD09-00301
| FIRE-Final Inspection | 7/7/2009 | 7/8/2009 | 7/8/2009 4:50:59 PM | A | PART |
|
|
See red-lines on plans for racking installation completed and okayed to date. Tenant to provide one additional fire extinguisher and shelf load limit signage at the second level mezzanine as discussed.
|
FIR09-00052
| FIR-Aging Inspection | 7/8/2009 | 7/8/2009 | 7/8/2009 12:50:23 PM | | DONE |
|
|
Work in progress, also pending site acceptance testing for interconnection to the new fire alarm system.
|
BLD08-01806
| FIRE-Final Inspection | 7/7/2009 | 7/8/2009 | 7/8/2009 12:44:49 PM | A | FAIL |
|
|
See fire code review notes items #2, 5, and 12 regarding fire dept. access requirements and posting of max. occupant load sign. Also refer to plan sheet a1.11 keynotes #24 and 25 annotated in red for fire lane access to be provided.
|
BLD09-00591
| BLD-Final | 7/6/2009 | 7/8/2009 | 7/8/2009 12:39:31 PM | A | PASS |
|
|
Fire life safety inspection completed acceptable.
|