ELE10-01520
| Electrical Rough-In | 7/8/2010 | 7/8/2010 | 7/8/2010 3:31:51 PM | P | PASS |
|
|
Job complete Inspection requested from web by: Stuart Welton ri ok
|
ELE10-01520
| Final | 7/8/2010 | 7/8/2010 | 7/8/2010 3:31:37 PM | P | PASS |
|
|
Job complete Inspection requested from web by: Stuart Welton ok
|
ELE10-01511
| Rough-In Permanent Service | 7/8/2010 | 7/8/2010 | 7/8/2010 3:27:51 PM | P | PASS |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### corrections made, ri ok, p/s u/g n ok
|
ELE10-01456
| Electrical Rough-In | 7/8/2010 | 7/8/2010 | 7/8/2010 2:31:32 PM | P | PASS |
|
|
Inspection requested from web by: Rhonda Yoast Phone #: ###-#### ri ok
|
ELE10-01455
| Electrical Rough-In | 7/8/2010 | 7/8/2010 | 7/8/2010 1:38:49 PM | P | PASS |
|
|
Inspection requested from web by: Rhonda Yoast Phone #: ###-#### called, ri ok
|
ELE10-01518
| Electrical Rough-In | 7/8/2010 | 7/8/2010 | 7/8/2010 12:41:20 PM | P | PASS |
|
|
Andy Phone #: ###-#### ri ok
|
ELE10-01518
| Final | 7/8/2010 | 7/8/2010 | 7/8/2010 12:40:49 PM | P | PASS |
|
|
Andy Phone #: ###-#### ok final
|
ELE10-01418
| Electrical Rough-In | 7/2/2010 | 7/8/2010 | 7/8/2010 12:16:52 PM | P | PASS |
|
|
Job completed Inspection requested from web by: Stuart Welton ri ok
|
ELE10-01418
| Final | 7/8/2010 | 7/8/2010 | 7/8/2010 12:16:34 PM | P | PASS |
|
|
Job completed Inspection requested from web by: Stuart Welton ok final
|
ELE10-01514
| Electrical Rough-In | 7/7/2010 | 7/8/2010 | 7/8/2010 10:36:38 AM | A | PASS |
|
|
Inspection requested from web by: kendall bender Phone #: ###-#### ri ok
|
ELE10-01514
| Final | 7/8/2010 | 7/8/2010 | 7/8/2010 10:36:20 AM | A | PASS |
|
|
Inspection requested from web by: kendall bender Phone #: ###-#### ok to final
|
ELE10-01499
| Permanent Service | 7/7/2010 | 7/8/2010 | 7/8/2010 10:31:13 AM | A | PASS |
|
|
If you have any questions, please give Clay a call. Thanks! Inspection requested from web by: Clay Morgan Phone #: ###-#### p/s o/h rec ok
|
ELE10-01492
| Permanent Service | 7/7/2010 | 7/8/2010 | 7/8/2010 10:02:06 AM | A | PASS |
|
|
If you have any questions, please give Clay a call. Thank You. Inspection requested from web by: Clay Morgan Phone #: ###-#### p/s o/h rec ok
|
ELE10-01511
| Rough-In Permanent Service | 7/7/2010 | 7/8/2010 | 7/8/2010 9:23:04 AM | A | FAIL |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called, left message, left correction notice, NEC 334.23 shall protect cables within 6' of attic access- upper, 314.20 boxes shall be flush with finished surface in combustile walls
|
ELE10-01509
| Electrical Rough-In | 7/7/2010 | 7/8/2010 | 7/8/2010 8:38:11 AM | A | PASS |
|
|
Re-inspect for rough of walls. Contact is Jay Sprik. Inspection requested from web by: Richard Montgomery Phone #: ###-#### corrections made, ok cover walls only
|
ELE10-01472
| Conference | 7/7/2010 | 7/8/2010 | 7/8/2010 8:03:39 AM | A | DONE |
|
|
Would like to talk to you about signal cabling running under raised floors in our Fab areas. Article 300.22B, C & D. Paul Cook Inspection requested from web by: Paul Cook Phone #: ###-#### talked about nec for cabling under raised floors per 300 and 645, interpretation does not allow basket type wireways under floor unless all cable plenum rated
|
ELE09-01834
| DOC - Permit Expired | 7/8/2010 | 7/8/2010 | 7/8/2010 6:36:10 AM | A | PASS |
|
|
no activity
|
ELE09-01611
| DOC - Permit Expired | 7/8/2010 | 7/8/2010 | 7/8/2010 6:34:43 AM | A | PASS |
|
|
no activity
|
ELE09-02368
| ELE-Aging Inspection | 7/8/2010 | 7/8/2010 | 7/8/2010 6:33:13 AM | | DONE |
|
|
see doc expire
|
ELE09-02368
| DOC - Permit Expired | 7/8/2010 | 7/8/2010 | 7/8/2010 6:33:00 AM | A | PASS |
|
|
no activity
|
ELE09-02373
| ELE-Aging Inspection | 7/8/2010 | 7/8/2010 | 7/8/2010 6:31:43 AM | | DONE |
|
|
see doc expire
|
ELE09-02373
| DOC - Permit Expired | 7/8/2010 | 7/8/2010 | 7/8/2010 6:31:28 AM | A | PASS |
|
|
no activity
|
ELE08-02505
| ELE-Aging Inspection | 7/8/2010 | 7/8/2010 | 7/8/2010 6:30:03 AM | | DONE |
|
|
see doc expire
|
ELE08-02505
| DOC - Permit Expired | 7/8/2010 | 7/8/2010 | 7/8/2010 6:29:47 AM | A | PASS |
|
|
no activity
|
ELE08-02502
| ELE-Aging Inspection | 7/8/2010 | 7/8/2010 | 7/8/2010 6:28:03 AM | | DONE |
|
|
see doc expire
|
ELE08-02502
| DOC - Permit Expired | 7/8/2010 | 7/8/2010 | 7/8/2010 6:27:49 AM | A | PASS |
|
|
no activity
|
ELE10-01504
| Rough-In Permanent Service | 7/7/2010 | 7/8/2010 | 7/7/2010 3:53:44 PM | A | CANC |
|
|
Inspection requested from web by: Rowdy Monroe Phone #: ###-#### Inspection cancelled from web by: Rowdy Monroe
|