FIR09-00375
| FIR-Aging Inspection | 7/8/2011 | 7/8/2011 | 7/8/2011 4:38:11 PM | | FAIL |
|
|
Failed inspection 2/23.
|
FIR10-00583
| INSP-Sprinkler Rough-in | 7/8/2011 | 7/8/2011 | 7/8/2011 4:36:24 PM | P | FAIL |
|
|
Inspection for the attic area and the 2nd floor completed. Noted items include; 3 blocked upright heads at class 207, 4 overspaced pendent heads at class 207, one overspaced ssu at class 207, one blocked ssu and ssp at room 202, missing longitudinal brace at 202, elevator hoistway may require at sprinkler head at the top due to car construction, painted head at the SW stairway, 4 overspaced heads from an adjacent wall at classrooms 212 and 211, beam obstruction at hall 205, library work room and class 204 have overspaced upright coverage as measured along the slope, noted 13 blocked upright heads at sprigs in the attic area, 4 sprigs are overspaced off adjacent walls (2@ 9'/ 2@12') ,upright deflectors at some locations are in direct contact with the ceiling. See plans for red-line notes pertaining.
|
BLD11-00760
| FIRE-Conference | 7/8/2011 | 7/8/2011 | 7/8/2011 4:18:40 PM | P | DONE |
|
|
Regarding exit signage.
|
FIR11-00225
| INSP-Final Inspection | 7/8/2011 | 7/8/2011 | 7/8/2011 4:17:54 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR11-00186
| INSP-Sprinkler Rough-in/Hydro | 7/8/2011 | 7/8/2011 | 7/8/2011 4:17:20 PM | P | PART |
|
|
Pre-inspection for work at life test #1 and the NN room completed.
|
FIR11-00227
| INSP-Sprinkler Rough-in | 7/7/2011 | 7/8/2011 | 7/8/2011 1:58:35 PM | A | PART |
|
|
Overhead fire sprinkler system modifications are approved for cover at the drop ceiling areas within the tenant remodel.
|
BLD11-01426
| FIRE-Final Inspection | 7/7/2011 | 7/8/2011 | 7/8/2011 1:57:27 PM | A | PASS |
|
|
Field verified correction items are finished, life safety is acceptable pending vent infill and paper faced insulation is concealed- to be done prior to structural final as discussed.
|
FIR11-00225
| INSP-Alarm Testing | 7/7/2011 | 7/8/2011 | 7/8/2011 1:55:15 PM | A | PART |
|
|
New fire alarm panel tested satisfactory.
|
FIR11-00282
| INSP-Sprinkler Rough-in | 7/7/2011 | 7/8/2011 | 7/8/2011 1:53:48 PM | A | PART |
|
|
Okay to cover the remainder of overhead sprinkler work. Final pending tile, escutcheons, and removal of temporary construction partitions.
|