Inspections for the day of: Friday, July 8, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00375 FIR-Aging Inspection7/8/20117/8/20117/8/2011 4:38:11 PM FAIL
Failed inspection 2/23.
FIR10-00583 INSP-Sprinkler Rough-in7/8/20117/8/20117/8/2011 4:36:24 PMPFAIL
Inspection for the attic area and the 2nd floor completed. Noted items include; 3 blocked upright heads at class 207, 4 overspaced pendent heads at class 207, one overspaced ssu at class 207, one blocked ssu and ssp at room 202, missing longitudinal brace at 202, elevator hoistway may require at sprinkler head at the top due to car construction, painted head at the SW stairway, 4 overspaced heads from an adjacent wall at classrooms 212 and 211, beam obstruction at hall 205, library work room and class 204 have overspaced upright coverage as measured along the slope, noted 13 blocked upright heads at sprigs in the attic area, 4 sprigs are overspaced off adjacent walls (2@ 9'/ 2@12') ,upright deflectors at some locations are in direct contact with the ceiling. See plans for red-line notes pertaining.
BLD11-00760 FIRE-Conference7/8/20117/8/20117/8/2011 4:18:40 PMPDONE
Regarding exit signage.
FIR11-00225 INSP-Final Inspection7/8/20117/8/20117/8/2011 4:17:54 PMPPASS
Fire alarm permit finaled.
FIR11-00186 INSP-Sprinkler Rough-in/Hydro7/8/20117/8/20117/8/2011 4:17:20 PMPPART
Pre-inspection for work at life test #1 and the NN room completed.
FIR11-00227 INSP-Sprinkler Rough-in7/7/20117/8/20117/8/2011 1:58:35 PMAPART
Overhead fire sprinkler system modifications are approved for cover at the drop ceiling areas within the tenant remodel.
BLD11-01426 FIRE-Final Inspection7/7/20117/8/20117/8/2011 1:57:27 PMAPASS
Field verified correction items are finished, life safety is acceptable pending vent infill and paper faced insulation is concealed- to be done prior to structural final as discussed.
FIR11-00225 INSP-Alarm Testing7/7/20117/8/20117/8/2011 1:55:15 PMAPART
New fire alarm panel tested satisfactory.
FIR11-00282 INSP-Sprinkler Rough-in7/7/20117/8/20117/8/2011 1:53:48 PMAPART
Okay to cover the remainder of overhead sprinkler work. Final pending tile, escutcheons, and removal of temporary construction partitions.