Inspections for the day of: Friday, July 8, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00159 INSP-Sprinkler Rough-in7/7/20117/8/20117/8/2011 3:24:05 PMPPART
The majority of the area looked at this afternoon was the Upper Level. There are still several outstanding items which include missing retaining straps, overspaced heads, missing heads, need for trapeze hangers in the warehouse and possible obstructions caused by the valances in the display areas. The piping arrangement does not match the plans so plan modifications will be required prior to a final sign off. The lower level truck dock dry system was inspected today as well. Revised hydraulic calculations were submitted and approved by Tim Frost for this area. I need verification that the top beam clamps have been welded to the beam flange or new hangers installed. Tim Frost noted a Trash Compactor area which is lacking sprinkler protection.
FIR11-00082 INSP-Final Inspection7/7/20117/8/20117/8/2011 3:17:54 PMAPASS
Permit finaled.
FIR11-00159 INSP-Sprinkler Rough-in7/7/20117/8/20117/8/2011 11:15:13 AMAPASS
The second floor elevator room and the area around the escalator, at the second floor, is ok to cover.
FIR11-00095 INSP-Sprinkler Rough-in/Hydro7/7/20117/8/20117/8/2011 11:13:44 AMAPART
Todays inspection was for the second floor of the office area. There were two retaining strap issues and the 3" sprinkler main was missing all of the trapeze hangers. The hardlid area in the north east corner is ok to cover. Also a separate inspection will be required when the arm-overs and drops have been installed in the gridded ceiling areas.
FIR11-00238 INSP-Sprinkler Rough-in7/7/20117/8/20117/8/2011 11:00:27 AMAPASS
The piping in the modified soffit area is ok to cover.
BLD11-00165 FIRE-Final Inspection7/8/20117/8/20117/8/2011 12:00:00 AMPCANC
jack Phone #: ###-####
BLD11-00164 FIRE-Final Inspection7/8/20117/8/20117/8/2011 12:00:00 AMPCANC
jack Phone #: ###-####