Inspections for the day of: Tuesday, July 8, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC14-02745 Final7/4/20147/8/20147/8/2014 4:43:54 PMPPASS
Please Call Robbie ###-#### @ Jims Heating Prior To Inspection Thank You Phone #: ###-#### >> Inspection requested via web by Manuel Acuna
MEC14-02782 Final7/7/20147/8/20147/8/2014 4:13:07 PMPNR
Please do a flu inspection test. please contact Eric with any further questions - ###-#### Phone #: ###-#### >> Inspection requested via web by Bailey Esposito
MEC14-02608 Final7/1/20147/8/20147/8/2014 3:40:01 PMPPASS
This is a gas line pressure test, Flue Pressure and Final Inspect. Pls meet our installer at home at 1:00 PM . Install Mgr, Allen, Ph is ###-####.
Phone #: ###-#### >> Inspection requested via web by Mary LaFayette
MEC14-02768 Final7/7/20147/8/20147/8/2014 3:18:23 PMPPASS
Please call Jean prior to arrival ###-####. Inspect 50 gal gas w/h. Phone #: ###-#### >> Inspection requested via web by James Staley
MEC14-02665 Final7/8/20147/8/20147/8/2014 2:41:45 PMPPASS
CALL ###-#### WITH ISSUES Thanks Joe Bertwell Phone #: ###-#### >> Inspection requested via web by Joe Bertwell
MEC14-02793 Conference7/8/20147/8/20147/8/2014 2:11:45 PMPPASS
Flue Test & Final Inspection- Please have inspector call Aaron the installer to meet for the flue test ###-#### Phone #: ###-#### >> Inspection requested via web by Carolyn Rudd
MEC14-02251 Final7/8/20147/8/20147/8/2014 1:43:49 PMPPASS
installer sam ###-#### Phone #: ###-#### >> Inspection requested via web by Dustin Rich
MEC14-01147 Final7/8/20147/8/20147/8/2014 1:26:55 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN - need to support line sets on exterior of building, need to complete air balance on the units. reschedule when done.
MIS14-00153 MEC-Conference7/7/20147/8/20147/8/2014 12:22:21 PMAFAIL
After 10 am please-Fred***For Occupancy Phone #: ###-#### - Class 1 hood needs to extend 6" beyond the cooking equipment, currently the cooking equipment extends out past the hood. Grease duct for class 1 hood is not ran in approved material, needs to be changed out to meet code. Need stainless steel between class 1 hood & wall, on wall under hood, stainless steel needs to extend 18" out from edge of class 1 hood. Need make-up air for class 1 hood. Need econmizer for roof top unit. Need to support gas pipe on roof. Any exhaust or plumbing vents need to terminate 10' away or 3' above fresh air openings when make-up air, and economizer are installed.
MEC14-01853 Final7/7/20147/8/20147/8/2014 10:44:58 AMAPASS
Please call Cathy the homeowner B4 arrival. Phone #: ###-#### >> Inspection requested via web by Lisa Whitney
MEC14-02608 Final7/1/20147/8/20147/1/2014 4:47:57 PMPCANC
This is a Flue Pressure and Final Inspect. Pls meet our installer
at home at 1:00 PM .
Install Mgr, Allen, Ph is ###-####.
Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette