Inspections for the day of: Wednesday, July 8, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01863 Final7/7/20157/8/20157/8/2015 5:35:32 PMPFAIL
Phone #: ###-#### Inspection requested via web by shane miller Overcurrent device over ampacity of subpanel feeders, Need to strap service raiser, NEC 408.41Terminate one neutral conductor per lug. Provide equipment grounding conductor for A/C branch circuit, Secure branch circuits at subpanel within 12in.
ELE13-00701 Final7/8/20157/8/20157/8/2015 4:46:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Rick Berry UL Listed sign, final ok
ELE15-02089 Final7/8/20157/8/20157/8/2015 4:36:30 PMPPASS
correction done, final ok
ELE13-00702 Final7/8/20157/8/20157/8/2015 4:32:33 PMPNH
Phone #: ###-#### Inspection requested via web by Andy Rose No access, left message on door of permit lacking final inspection
ELE14-01066 Electrical Rough-In7/7/20157/8/20157/8/2015 3:18:45 PMPPASS
ceilings in rooms H207-H213, walls in rooms H361, H362, H364, H373, H315, H314, H301 Phone #: ###-#### Inspection requested via web by Fabian Luna rough-in ok cover as per noted
ELE13-00745 ELE-Aging Inspection7/8/20157/8/20157/8/2015 12:18:37 PM DONE
see final
ELE13-00745 Final7/8/20157/8/20157/8/2015 12:18:03 PMPPASS
job completed, final ok
ELE15-02089 Electrical Rough-In7/7/20157/8/20157/8/2015 12:03:21 PMAFAIL
Add 30 amp AC job complete. Final needed Phone #: ###-#### Inspection requested via web by Stuart Welton NEC 334.12(A)(4) NM cable shall not be used in wet or damp locations
ELE15-01609 Temporary Service7/7/20157/8/20157/8/2015 9:57:33 AMACANC
Temp Occupancy inspection
please call lance if you have questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott
ELE15-01609 Final7/8/20157/8/20157/8/2015 9:55:39 AMPNR
Temp Occupancy inspection
please call lance if you have questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott Not ready at this time for partial final