ELE12-02027
| ELE-Aging Inspection | 7/8/2016 | 7/8/2016 | 7/8/2016 2:38:57 PM | | CANC |
|
|
|
ELE12-02026
| ELE-Aging Inspection | 7/8/2016 | 7/8/2016 | 7/8/2016 2:38:31 PM | | CANC |
|
|
|
ELE16-02168
| Rough-In Permanent Service | 7/8/2016 | 7/8/2016 | 7/8/2016 2:37:50 PM | P | PASS |
|
|
Please inspect the service Phone #: ###-#### Inspection requested via web by Spencer McLean Underground rough in ok cover Verizon p/s u/g n ok
|
ELE16-02148
| Electrical Rough-In | 7/7/2016 | 7/8/2016 | 7/8/2016 2:18:30 PM | P | PASS |
|
|
Garage door should be unlocked Phone #: ###-#### Inspection requested via web by Troy Cobb Drysheeting not on roof told it is happening Friday afternoon, will drive by Monday to confirm wiring protected if not rewire will be required. Garage rough in ok cover
|
ELE15-00495
| Electrical Rough-In | 7/8/2016 | 7/8/2016 | 7/8/2016 1:27:32 PM | P | PASS |
|
|
Ceiling inspections elevator lobbies. Contact is Eric Gibson ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves Called contact no answer signed book on 7th and 8th floor elevator lobby ceilings rough in ok cover
|
ELE15-03901
| Electrical Rough-In | 7/8/2016 | 7/8/2016 | 7/8/2016 12:33:48 PM | A | PASS |
|
|
Call Pierce for r/i inspection of 9th floor soffit. Phone #: ###-#### Inspection requested via web by Rafael Castillo 9th fl conference rm soffit as noted in book rough in ok cover
|
ELE16-01838
| Electrical Rough-In | 7/7/2016 | 7/8/2016 | 7/8/2016 11:40:27 AM | A | PASS |
|
|
Level 9 Room # 924, 923, 922,925,926,927,919,920,916,928,915,929,932, 933,934,935 Phone #: ###-#### Inspection requested via web by Tom Betty Walls for rooms as noted rough in ok cover
|
ELE16-02151
| Electrical Rough-In | 7/7/2016 | 7/8/2016 | 7/8/2016 10:51:22 AM | A | PASS |
|
|
Larry Phone #: ###-#### Discussed mounting basement lights to bottom of flooring which is 4+" thick OK, future solar EMT conduit preran from roof to crawl space. Service at future date. Rough in ok cover
|
ELE16-02104
| Temporary Service | 7/7/2016 | 7/8/2016 | 7/8/2016 10:14:26 AM | A | PASS |
|
|
Re-inspection on the temp power pole. Contact Craig Timmons @ ###-#### Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s o/h n ok
|
ELE16-01551
| Electrical Rough-In | 7/7/2016 | 7/8/2016 | 7/8/2016 8:36:33 AM | A | PASS |
|
|
Mark-partial interior walls Phone #: ###-#### Discussed GFCI device shall be readily accessible for operational jetted tubs. 1st floor wall rough in ok cover
|