Inspections for the day of: Wednesday, July 8, 2020.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorGreg Ruxton
TitleFIRE CODE PLAN EXAMINER
Phone #208-608-7058
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00476 INSP-Final Inspection7/7/20207/8/20207/8/2020 2:19:13 PMAPASS
Hood functions tested to include shutdown of electrical circuits, puff test, pull station, thermal link activation and location of Class K FE.

At time of inspection no gas fired or grease and smoke generating appliances were installed under the hood. Gas lines capped off for possible future expansion. All currently installed appliances electric and consist of two steam kettles, an oven and a steam cabinet. Any future additions or changes of hood applianc(s) will require a seperate permit.

Final inspection of a new Ansul R102 6.0 gallon fire suppression system. Phone #: ###-#### Inspection requested via web by Don Kartchner
NAF20-00044 INSP-Final7/8/20207/8/20207/8/2020 12:27:37 PMPDONE
Passed for occupancy fire life safety. Exit signs, emergency lighting, exterior exit illumination, door hardware and fire extinguisher placement code compliant. Address is 116 E 40th as noted in actual permit not 10482 W Carlton Bay Dr as indicated on Inspectors Module.

Call prior to going Phone #: 2086314980 >> Inspection requested via mobile web by Kevin Burke
BLD19-00658 FIRE-Final Inspection7/7/20207/8/20207/8/2020 11:41:54 AMAPASS
Fire Life Safety inspection passed. Building inspector to verify main entry doors panic hardware is code compliant for egress and over rides electric strike card reader once system is fully operational.

Josh *screened* Phone #: ###-####
FIR20-00056 INSP-Final Inspection7/7/20207/8/20207/8/2020 11:41:53 AMAPASS
Notification appliances, voice annunciation system, initiating devices and air handler shutdown passed testing and inspection.

Buck Tom Phone #: ###-#### Inspection requested via web by Ken Webster