Inspections for the day of: Wednesday, July 9, 1997.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-01959 INSP - Temporary service7/9/19977/9/19977/9/1997 12:00:00 AM PASS
/ / 315 - 49 ok jf o/h new
ELE97-02217 INSP - Ele Rough-In/Perm Svc7/8/19977/9/19977/9/1997 12:00:00 AMAPASS
07/09/97 315 - 09&53 ok jf 13rms 1a/c 200a u/g new
ELE97-02230 INSP - Ele Rough-In/Perm Svc7/8/19977/9/19977/9/1997 12:00:00 AMACANC
07/09/97 315 - nr jf see added 01 inspection
ELE96-01775 INSP - Electrical Rough-In7/8/19977/9/19977/9/1997 12:00:00 AMAPART
ceiling clouds 09 ok jf
ELE97-01701 INSP - Hot Tubs/Spas7/8/19977/9/19977/9/1997 12:00:00 AMANH
07/09/97 315 - nalc jf
ELE97-01959 INSP - Final7/8/19977/9/19977/9/1997 12:00:00 AMAPASS
07/09/97 315 - 14 ok jf
ELE97-01187 INSP - Electrical Rough-In7/9/19977/9/19977/9/1997 12:00:00 AMPPART
07/09/97 315 - grounding and ceiling cover 09 ok jf
ELE97-01701 INSP - Hot Tubs/Spas7/9/19977/9/19977/9/1997 12:00:00 AMPPASS
07/09/97 315 - SHE IS THERE SHE WAS THERE AM PLEASE GO TO BACK YARD IF N DOOR 09 for spa ok jf 1 spa
ELE97-02239 INSP - Permanent service7/9/19977/9/19977/9/1997 12:00:00 AMPFAIL
07/09/97 315 - 53 failed jf cor. posted NEC, 110-14 needs kool aid on al clearence for new panels a&b 250-92(b) GEC needs connector or non metall bushings, 250-81 grd to metal water system, 250-94 needs 1/0 cu. or 3/0