Inspections for the day of: Tuesday, July 9, 2002.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00211 INSP-Final Inspection7/5/20027/9/20027/9/2002 12:00:00 AMAFAIL
provide label in the fire alarm panel for the main breaker location, provide verification that the smoke detector is compatible with the fire alarm panel (its different from the cut sheets), block off spare outlet on the dedicated circuit, install correct orfice in the inspectors test outlet, test flow switch and 4" overhead valve, provide "knox box" 7/9/2002 2:35:28 PM
BLD01-03127 FIRE-Final Inspection7/8/20027/9/20027/9/2002 12:00:00 AMAFAIL
provide building address, unit address, fire extinguishers and fire caulk penatrations made by the water heaters 7/9/2002 9:49:35 AM
FIR02-00264 INSP-Final Inspection7/9/20027/9/20027/9/2002 12:00:00 AMPFAIL
provide verification that the flame spread rate for the fiberglass backing is less than 25 or add upright protection, pendant sprinkler heads appear to be overspaced above the mezzanine (130 max), provide inspection tag for riser and facp 7/9/2002 4:01:45 PM