ELE07-02405
| Electrical Rough-In | 7/6/2007 | 7/9/2007 | 7/9/2007 4:02:22 PM | P | CANC |
|
|
john - underground Phone #: ###-#### talked with contr ne needs to cancel , gen. contr not ready
|
ELE07-02064
| Electrical Rough-In | 7/9/2007 | 7/9/2007 | 7/9/2007 3:16:38 PM | P | PART |
|
|
jerod Note: underground Phone #: ###-#### u/g for parking lot lignts anop
|
ELE07-02313
| Rough-In Permanent Service | 7/9/2007 | 7/9/2007 | 7/9/2007 2:20:25 PM | P | PASS |
|
|
electrician is Tony Norton, needs ground inspected for permanent service Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer electrode ok for dirt cover and p/s o/h rec. ok
|
ELE07-01367
| Electrical Rough-In | 7/9/2007 | 7/9/2007 | 7/9/2007 1:56:50 PM | P | FAIL |
|
|
david; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang not ready too many violations and conference only ok
|
ELE07-01258
| Final | 7/9/2007 | 7/9/2007 | 7/9/2007 12:54:44 PM | P | PASS |
|
|
Journeyman-Jerry ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE07-02410
| Permanent Service | 7/6/2007 | 7/9/2007 | 7/9/2007 11:07:01 AM | A | PASS |
|
|
200amp service upgrade, any questions call Jimmy @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose p/s o/h rec. ok
|
ELE07-02410
| Final | 7/9/2007 | 7/9/2007 | 7/9/2007 11:06:38 AM | A | PART |
|
|
200amp service upgrade, any questions call Jimmy @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok
|
ELE07-02005
| Final | 7/8/2007 | 7/9/2007 | 7/9/2007 10:42:11 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 7/8/2007 at 7:57:03 PM. Contact: ###-####. corr 250.122 shall not use #12 for 30amp W H circuits from panel tp WH and all jboxes called
|
ELE07-00904
| Final | 7/6/2007 | 7/9/2007 | 7/9/2007 10:09:12 AM | A | FAIL |
|
|
jason - swimming pool; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corr. called 110.26(F)(2) needs clearence for panel fence and hydraulic lines in the way, 250.199 shall not ID #6 or smaller equip grd, 680.24 shall provide listed pool light box for pool fixture shall not terminate cord into panel for pool equipment
|
ELE07-02396
| Electrical Rough-In | 7/5/2007 | 7/9/2007 | 7/9/2007 9:08:07 AM | A | PASS |
|
|
calvin; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang r/i ok
|
ELE07-02323
| Electrical Rough-In | 7/6/2007 | 7/9/2007 | 7/9/2007 8:20:44 AM | A | PART |
|
|
Electrical cover inspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers u/g ok only, no e grid
|