ELE07-02343
| Electrical Rough-In | 7/9/2007 | 7/9/2007 | 7/9/2007 5:14:48 PM | P | FAIL |
|
|
rick; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang corrections nec312.5(C) all cable shall enter box with approved connectors. nec314.17(C)exception all cable shall be supported within 8inch of non metallic box called
|
ELE07-01604
| Final | 7/9/2007 | 7/9/2007 | 7/9/2007 3:23:06 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok final
|
ELE07-02340
| Final | 7/9/2007 | 7/9/2007 | 7/9/2007 2:13:07 PM | P | PASS |
|
|
please call Aaron White so he can meet you there Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok final
|
ELE07-02353
| Rough-In Permanent Service | 7/6/2007 | 7/9/2007 | 7/9/2007 1:22:07 PM | A | PART |
|
|
electrician is Jon Fivecoat Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok cover ri did not look at service not ready
|
ELE07-02384
| Final | 7/6/2007 | 7/9/2007 | 7/9/2007 11:45:18 AM | A | PASS |
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok final
|
ELE07-02407
| Electrical Rough-In | 7/6/2007 | 7/9/2007 | 7/9/2007 10:31:36 AM | A | PASS |
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok cover ri
|
ELE07-02347
| Final | 7/2/2007 | 7/9/2007 | 7/9/2007 9:36:42 AM | A | PASS |
|
|
Final inspection of 10 relocated and upgraded tools in building 26 for SUP03 # ###-#### Phone #: ###-#### Internet Inspection Request from: Del Elwood ok final
|