ELE08-00263 Electrical Rough-In7/9/20087/9/20087/9/2008 4:21:09 PMPPART
Bruce- ceiling Phone #: ###-#### ok cover ceiling except for xray room
ELE08-01869 Permanent Service7/9/20087/9/20087/9/2008 4:20:15 PMPPASS
mohammadi Phone #: ###-#### p/s o/h reconnect ok note needs final tomorrow note no esc permit in project
ELE07-03471 Final7/8/20087/9/20087/9/2008 4:19:38 PMPFAIL
wayne - late afternoon please Phone #: ###-#### corrections nec400.8(1,2,5,6,&7) nec110.3(B) shall follow manufactors instruction listing & labling (power poles) nec310.15 shall follow table 310.15(B)(2)(a) for derating (power poles) note esc permit finaled
ELE07-03315 Final7/9/20087/9/20087/9/2008 4:19:06 PMPPART
Matt Phone #: ###-#### all inside work completed just needs outside conduit inspection note parcel hold on esc permit
ELE08-01204 Electrical Rough-In7/9/20087/9/20087/9/2008 4:12:09 PMPPASS
Scheduled by a contractor via Hello! on 7/9/2008 at 9:01:17 AM. Contact: ###-####. ok cover walls only
ELE08-01869 Final7/9/20087/9/20087/9/2008 3:31:42 PMPCANC
mohammadi Phone #: ###-#### wrong type inspection
ESC08-00156 General Inspection7/9/20087/9/20087/9/2008 12:44:29 PMPPART
no sign-- site looks fine
ELE08-00588 Conference7/9/20087/9/20087/9/2008 12:43:18 PMPDONE
dan Phone #: ###-#### ok conf. makeup, stackits, staple, wall spacing, & ext. outlets
ELE08-01869 Conference7/8/20087/9/20087/9/2008 11:39:41 AMADONE
Abolfazle Phone #: ###-#### grounding isolated neut. main brker lock down note no esc permit in project
ELE07-02302 Electrical Rough-In7/8/20087/9/20087/9/2008 10:37:17 AMANR
CONTACT: STEVE HESS - PARTIAL FINAL AREAS E & F Phone #: ###-#### Internet Inspection Request from: Deb Gooden areas has to many things not completed
ESC07-00003 General Inspection7/9/20087/9/20087/9/2008 10:33:41 AMAPART
sign posted & site looked fine they started demo on old building
ELE08-01863 Electrical Rough-In7/8/20087/9/20087/9/2008 8:56:40 AMAPASS
Steve Phone #: ###-#### ok cover walls only note no esc permit in project