FIR12-00274
| INSP-Conference | 7/9/2012 | 7/9/2012 | 7/9/2012 3:45:42 PM | P | DONE |
|
|
Ceiling is ok to install from the west wall to the first column line.
|
FIR12-00274
| INSP-Final Inspection | 7/9/2012 | 7/9/2012 | 7/9/2012 3:43:34 PM | P | FAIL |
|
|
Inspection was actually a conference on what is required to fix the insulation blocking the upright sprinkler heads. We went over the NFPA 13 obstruction charts.
|
BLD12-01662
| FIRE-Final Inspection | 7/6/2012 | 7/9/2012 | 7/9/2012 2:34:41 PM | A | FAIL |
|
|
Mount and provide current inspection tag for the fire extinguisher, remove the thumbturn deadbolt on the main exit (keyed is ok), and provide the suite number.
|