Inspections for the day of: Tuesday, July 9, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00234 INSP-Sprinkler Rough-in7/9/20137/9/20137/9/2013 3:39:49 PMPPASS
Piping can be covered in the lay-in tile area.
FIR13-00280 INSP-Conference7/8/20137/9/20137/9/2013 3:25:48 PMADONE
Provide interconnection of the smoke detector with the fire alarm system per IFC 907.4, provide annual inspection report for the fire alarm system and provide dedicated circuit for the facp and the AES panel
FIR12-00663 FIR-Aging Inspection7/9/20137/9/20137/9/2013 2:50:41 PM PASS
FIR12-00538 FIR-Aging Inspection7/9/20137/9/20137/9/2013 2:38:54 PM DONE
work is in progress
BLD13-01514 FIRE-Final Inspection7/8/20137/9/20137/9/2013 2:34:13 PMPFAIL
With the removal of the wall two sprinkler heads are now too close to one another. When this is addressed the life safety can be finaled.
BLD13-00126 FIRE-Final Inspection7/8/20137/9/20137/9/2013 1:57:07 PMPPASS
life safety passed
FIR13-00281 INSP-Sprinkler Rough-in7/8/20137/9/20137/9/2013 1:00:30 PMAPASS
sprinkler piping is ok to cover.
FIR12-00583 INSP-Supply line flush7/8/20137/9/20137/9/2013 10:31:41 AMAPASS
Performed six underground flushes for the remaining buildings. All six passed.