FIR13-00725
| INSP-Sprinkler Rough-in/Hydro | 7/9/2015 | 7/9/2015 | 7/9/2015 3:33:32 PM | P | PART |
|
|
Test of wet and dry pipe fire sprinkler systems, including fire alarm interface, including tampers, waterflows, low-air tests and dry pipe valve trip tests for A/G parking garage (levels 1 thru 5) and associated wet systems, including Makers room and 5th floor wet system. All dry-pipe and wet pipe systems alarmed within 60 seconds. All other fire alarm interface signals came in OK. NOTE: U/G parking garage under separate permit, and not tested this visit. Fire pump is also under this other permit (U/G PG).
|
FIR14-00365
| INSP-Final Inspection | 7/8/2015 | 7/9/2015 | 7/9/2015 3:27:05 PM | P | PART |
|
|
Inspection of Helix dry-pipe systems for fire alarm interface, including water flows, tampers, low-air signals and including trip tests - all floors except levels 2 and 3. All tested OK and within 60 seconds of flow test. NOTE: 6th floor wet system not programed into alarm system - will retest.
|