Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00725 INSP-Sprinkler Rough-in/Hydro7/9/20157/9/20157/9/2015 3:33:32 PMPPART
Test of wet and dry pipe fire sprinkler systems, including fire alarm interface, including tampers, waterflows, low-air tests and dry pipe valve trip tests for A/G parking garage (levels 1 thru 5) and associated wet systems, including Makers room and 5th floor wet system.
All dry-pipe and wet pipe systems alarmed within 60 seconds. All other fire alarm interface signals came in OK.
NOTE: U/G parking garage under separate permit, and not tested this visit. Fire pump is also under this other permit (U/G PG).
FIR14-00365 INSP-Final Inspection7/8/20157/9/20157/9/2015 3:27:05 PMPPART
Inspection of Helix dry-pipe systems for fire alarm interface, including water flows, tampers, low-air signals and including trip tests - all floors except levels 2 and 3.
All tested OK and within 60 seconds of flow test.
NOTE: 6th floor wet system not programed into alarm system - will retest.