Inspections for the day of: Monday, July 9, 2018.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDan Ediger
TitlePLM-INSPECTOR
Phone #869-5166
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM17-03918 PLM-Aging Inspection7/9/20187/9/20187/10/2018 3:42:12 PM DEFR
Left a message to call me back or call for a final
PLM18-01473 Final7/9/20187/9/20187/9/2018 2:46:12 PMPFAIL
Alan Phone #: ###-####.
1. The T&P drain isn't glued.
2. The gas line cannot run in front of the water softener.
3. The water softener drain must have a min. of a 1" air gap at the termination point.
PLM18-02788 Water Heater Final7/5/20187/9/20187/9/2018 2:14:21 PMPFAIL
If you can contact homeowner Julia when 30 mins in route at ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Jennifer Alcala.
1. Pipe the pan drain to the outside of the house.
2. The t&p must be hard piped.
3. An electrical disconnect must be installed at the heater or a lockout at the breaker.
4. Make a proper electrical connection to the water heater.
PLM18-02786 Final7/5/20187/9/20187/9/2018 1:30:01 PMPPASS
Please call Donald Clayton prior to inspection at ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
PLM18-00613 Final7/9/20187/9/20187/9/2018 1:06:40 PMPPASS
Anthony Phone #: ###-####
PLM17-04672 Final7/9/20187/9/20187/9/2018 1:06:24 PMPPASS
Anthony Phone #: ###-####
PLM18-02699 Water Heater Final7/6/20187/9/20187/9/2018 9:53:35 AMAPASS
Please call Gail the owner when in route to home ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd