Inspections for the day of: Monday, July 9, 2018.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBen Livingston
TitleMEC-COM/RES INSPECTOR
Phone #576-1208
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-02057 Rough-in7/9/20187/9/20187/9/2018 4:10:26 PMPPASS
Re-inspection of the Rough In Phone #: ###-#### Inspection requested via web by Frank Marturello
MEC18-02337 Rough-in7/9/20187/9/20187/9/2018 3:24:37 PMPPASS
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN
MEC18-03209 Final7/9/20187/9/20187/9/2018 3:19:50 PMPPASS
Please call on way: Tyrel ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
MEC18-03137 Final7/6/20187/9/20187/9/2018 3:00:46 PMPFAIL
Please inspect as late as possible. Homeowner Harmony Wright, ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
per instalation instructions minimun flue size is 4", need to replace 3" pipe
MEC18-03153 Rough-in7/9/20187/9/20187/9/2018 1:54:50 PMPFAIL
requesting rough in inspection, gas pressure test also requested. This is open job site and I left my office number if any questions. Manual J should be onsite as well and after rough in the duct blast and balance are scheduled before final will be set up. My name is Steve if you have any questions. Phone #: ###-####
Inspection requested via web by Rick
no manual J onsite
MEC18-03153 Pressure Test7/9/20187/9/20187/9/2018 1:45:29 PMPPASS
gas line is pressured up and ready, open job site so should be able to access no problem. I listed Diamond Office number if any concerns or questions, my name is Steve Phone #: ###-#### Inspection requested via web by Rick Montgomery
20lb gas
MEC18-01260 Final7/9/20187/9/20187/9/2018 1:10:50 PMPPASS
Field Super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC18-01658 Pressure Test7/5/20187/9/20187/9/2018 11:19:20 AMAFAIL
L.L.-1, ; L-1, ; shaft piping, hydronic pressure test. If questions call Donny @ ###-####. Phone #: ###-#### Inspection requested via web by Stacia Haumann
walked parking garage and first floor hydronic 2 100lb tests, need approved plans on sight to pass inspection
MEC18-02900 Final7/6/20187/9/20187/9/2018 10:30:44 AMAFAIL
PLEASE CALL (HOMEOWNER) JOE @ # LISTED WHEN EN ROUTE FOR FINAL INSPECTION Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
need 6" fresh air to return plenum per manual J
MEC18-01162 Final7/6/20187/9/20187/9/2018 9:55:20 AMAPASS
Jared Phone #: ###-####
MEC18-02933 Final7/3/20187/9/20187/9/2018 9:43:19 AMAPASS
AM INSPECTIONS. INSTALLER TRAVIS: ###-####.
THIS IS TO WITNESS A FLUE PRESSURE TEST. CUSTOMER IS REQUEST HE TAKE NO MORE TIME OFF WORK FOR THIS. THANK YOU! Phone #: ###-#### Inspection requested via web by Aaron Alandt
5lb flue
MEC18-02671 Final7/6/20187/9/20187/9/2018 9:38:23 AMPCANC
Please call owner Amber when in route to home at ###-#### Phone #: ###-#### >> Inspection requested via web by Carolyn Rudd Inspection cancelled from web by: Carolyn Rudd
MEC18-01013 Rough-in7/6/20187/9/20187/9/2018 9:25:38 AMAPART
Rough in area B. Todd is your contact. please call 20 minutes prior. Phone #: ###-#### Inspection requested via web by Kim Adams
area b partial corridor and classrooms ok duct seal
MEC17-00228 Mec-Aging Inspection7/9/20187/9/20187/9/2018 8:46:54 AM CANC
MEC18-02798 Rough-in7/5/20187/9/20187/9/2018 8:46:10 AMAPASS
field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC18-02798 Pressure Test7/5/20187/9/20187/9/2018 8:45:52 AMAPASS
field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
20lb gas
MEC17-04668 Mec-Aging Inspection7/9/20187/9/20187/9/2018 8:38:10 AM CANC
MEC17-04668 DOC - Permit Finaled7/9/20187/9/20187/9/2018 8:38:04 AMPPASS
MEC16-05519 Mec-Aging Inspection7/9/20187/9/20187/9/2018 8:34:48 AM CANC