MEC18-02618
| Rough-in | 7/9/2018 | 7/9/2018 | 7/9/2018 4:34:35 PM | P | FAIL |
|
|
Please call on way: Darrius ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- flex ducting is being smash by floor joistes- need to have an approved Man J.
|
MEC18-03242
| Final | 7/9/2018 | 7/9/2018 | 7/9/2018 4:18:44 PM | P | NH |
|
|
PLEASE CALL ON WAY: jOSH ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- homeowner didnt want to let me in
|
MEC18-03106
| Rough-in | 7/9/2018 | 7/9/2018 | 7/9/2018 3:15:18 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
|
MEC18-03106
| Pressure Test | 7/9/2018 | 7/9/2018 | 7/9/2018 3:15:04 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 5lb flue ok- 20 lb gas ok
|
MEC18-03217
| Final | 7/9/2018 | 7/9/2018 | 7/9/2018 3:04:14 PM | P | FAIL |
|
|
Please call Maddie Phone #: ###-#### Inspection requested via web by Krista Boss - need electrical permit pulled before final -furnace ac coil co ok-
|
MEC18-03217
| Pressure Test | 7/9/2018 | 7/9/2018 | 7/9/2018 2:59:46 PM | P | PASS |
|
|
Please call Maddie Phone #: ###-#### Inspection requested via web by Krista Boss - 20lb gas pressure test ok
|
MEC18-03204
| Final | 7/6/2018 | 7/9/2018 | 7/9/2018 2:39:50 PM | P | NR |
|
|
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- not ready
|
MEC18-03204
| Pressure Test | 7/9/2018 | 7/9/2018 | 7/9/2018 2:39:27 PM | P | PASS |
|
|
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 5lb flue pressure test ok
|
MEC18-03223
| Rough-in | 7/6/2018 | 7/9/2018 | 7/9/2018 2:04:14 PM | A | PASS |
|
|
Zachary or the GC ###-#### Todd Phone #: ###-####- R/I ok need to transfer air or ducted return into new room at final
|
MEC18-02873
| Final | 7/6/2018 | 7/9/2018 | 7/9/2018 1:26:32 PM | P | PASS |
|
|
please call Jamie in route ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- furnace ac coil co ok
|
MEC18-02857
| Final | 7/9/2018 | 7/9/2018 | 7/9/2018 1:03:21 PM | P | PASS |
|
|
Manufactured home Phone #: ###-#### Inspection requested via web by jamie berg- A/C coil co ok
|
MEC18-03083
| Final | 7/3/2018 | 7/9/2018 | 7/9/2018 11:12:41 AM | A | FAIL |
|
|
can you please call when you are on the way. Customers name is Gordon Reed and his number is ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Marisa Hone- lineset at outdoor unit needs to be supported and 3.5" off the ground- need to pull a plumbing permit for the water heater
|
MEC18-03106
| Rough-in | 7/6/2018 | 7/9/2018 | 7/9/2018 10:09:09 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves -water heater flue in attic needs 1" clearances(flex duct is touching flue)- supply runs into master room, master bath, and bedroom 3 are being pinched by supports. need to adjust flex for a free flowing run to boots- supply trunk in attic needs duct seal at Y - 5lb flue pressure test fail gauge wont zero
|
MEC18-03106
| Pressure Test | 7/6/2018 | 7/9/2018 | 7/9/2018 10:05:57 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 5lb flue pressure test fail need to see gauge zero( replace gauage ) 20lb gas pressure ok
|
MEC18-02838
| Final | 7/3/2018 | 7/9/2018 | 7/9/2018 9:30:57 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette-lineset penetration needs sealed at outdoor unit
|
MEC18-03099
| Final | 7/3/2018 | 7/9/2018 | 7/9/2018 9:09:48 AM | A | FAIL |
|
|
This is an empty home - the gate code is 2663 - must enter the gate on the orchard side. Phone #: ###-#### Inspection requested via web by Sabrina DeHority- new lineset penetration at indoor unit needs sealed and the old penetration at the indoor unit needs sealed- want to see co detectors installed through out house- lineset penetration at outdoor unit needs sealed- need UV protection on lineset- want to see electrical permit pulled for new location of power for A/C- There is also a remodel being done on the west side where new duct work is being installed need to see your permit show OTHER and fees paid- call in next time for rough- in of duct work -Homeowners still live in house
|
MEC17-04659
| Mec-Aging Inspection | 7/9/2018 | 7/9/2018 | 7/9/2018 9:06:21 AM | | DONE |
|
|
house is still in rough- in phase- fireplace installer needs to call for final when the building process is complete
|
MEC18-03099
| Pressure Test | 7/3/2018 | 7/9/2018 | 7/9/2018 8:57:31 AM | A | FAIL |
|
|
This is an empty home - the gate code is 2663 - must enter the gate on the orchard side. Phone #: ###-#### Inspection requested via web by Sabrina DeHority- 5lb flue pressure test failed because gauge was at zero- also want to see the flue piping ran all the way to the furnace, looks like a few more fittings will be installed to make it to the furnace
|