FIR20-00393
| INSP-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 2:46:37 PM | P | PASS |
|
|
Permit finaled.
Gabe Torres is the contact. Thanks!! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00393
| INSP-Sprinkler Rough-in | 7/8/2020 | 7/9/2020 | 7/9/2020 2:46:08 PM | P | PASS |
|
|
Rough-in passed.
Gabe Torres is the contact. Thanks so much! (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00452
| INSP-Sprinkler Rough-in | 7/8/2020 | 7/9/2020 | 7/9/2020 2:13:02 PM | P | PASS |
|
|
See the city approved plans for locations/hardlids marked ok where piping is ok for cover.
Austin Farnworth is the contact. Thanks Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD20-00100
| FIRE-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 2:12:00 PM | A | PASS |
|
|
Life safety passed.
We are Looking for the fire/life safety final on the second and final phase of the project. I would like to meet you onsite if available.
Thanks Dana McCarter ###-#### Phone #: ###-#### Inspection requested via web by Drew Moorhouse
|
BLD20-01075
| FIRE-Conference | 7/9/2020 | 7/9/2020 | 7/9/2020 11:52:09 AM | A | DONE |
|
|
See the city approved plans for additional areas where insulation has been added.
Phone #: ###-#### Inspection requested via web by rick pew
|
FIR20-00264
| INSP-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 10:50:56 AM | A | PASS |
|
|
Permit finaled.
Please call our tech Mark McMillian at ###-#### to confirm a start time for this inspection. We would like it in the early AM if possible. Our electrician is Tri-State Electric. Robe Lawrence is our contact with them. His number is ###-####. Thank you. Phone #: ###-#### Inspection requested via web by James Schofield
|
BLD19-04004
| FIRE-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 10:13:25 AM | A | FAIL |
|
|
Provide additional fire extinguisher near main exit as discussed. Repair and provide testing of exit signs and emergency lights in the tenant space and the common corridor path of egress as discussed.
Zach *screened* Phone #: ###-####
|
BLD18-01806
| FIRE-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 10:12:11 AM | A | PASS |
|
|
Life safety passed.
SCREENED // Nick Phone #: ###-####
|
FIR20-00375
| INSP-Sprinkler Rough-in/Hydro | 7/9/2020 | 7/9/2020 | 7/9/2020 9:11:33 AM | A | FAIL |
|
|
Inspection turned into a walk-through/conference. I noted that the plans do need to be resubmitted for changes and a head needs to be added at the top fo the under/stairs to meet NFPA 13D 8.2.7. No piping to be covered yet. Could not do hydro since a head needs to be added.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-00316
| FIRE-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 8:33:05 AM | A | PASS |
|
|
Life safety passed for building 5. Phone #: ###-#### Inspection requested via web by chad stradley
|
FIR20-00476
| INSP-Final Inspection | 7/8/2020 | 7/9/2020 | 7/9/2020 6:53:36 AM | A | PASS |
|
|
Permit finaled by Greg. Retest on the hood fire suppression system. STEAM KETTLES ARE ELECTRIC!!!! NO GAS REQUIRED!! Thank you! Phone #: ###-#### Inspection requested via web by Don Kartchner
|