ELE02-02400
| Rough-In Permanent Service | 7/31/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | A | PART |
|
|
###-#### p/s o/h rec. ok 8/1/2002 1:45:39 PM
|
ELE02-02295
| Permanent Service | 7/31/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | A | FAIL |
|
|
###-#### cor. , do not cover, and $45.00 reinspection fee due posted called 300.4(A)(1)&(D) 330.30 strap MC 12 inches of boxes 358.30 strap emt 3ft of boxes, 314.20, 250.8 no SMS, 250.148 ues grd screws or clips 110.3(B) use manufactures listed buses at sub panel and service 8/1/2002 11:16:22 AM
|
ELE02-02403
| Final | 7/31/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | A | FAIL |
|
|
###-#### no access notice posted 8/1/2002 2:54:01 PM
|
ELE02-02369
| Electrical Rough-In | 7/31/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 07/31/2002 at 15:29:18. Contact: ###-####. ok 8/1/2002 12:37:38 PM
|
ELE02-02406
| Final | 7/31/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | A | NR |
|
|
###-#### al's did service and owner did rooms need to meet with contractor called left message no response 8/1/2002 6:12:06 PM
|
ELE02-02355
| Electrical Rough-In | 7/29/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | A | PASS |
|
|
###-#### a/c outside and new furnace in attic only 8/1/2002 3:56:08 PM
|
ELE02-02371
| Permanent Service | 7/31/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | PASS |
|
|
MITCH ###-#### Mitch will call for final when job is done
p/s u/g rec. ok 8/1/2002 5:15:28 PM
|
ELE99-02690
| Electrical Rough-In | 8/1/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | PART |
|
|
###-#### kent r/i ok see added p/s 8/1/2002 5:37:46 PM
|
ELE02-01822
| Final | 8/1/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | NR |
|
|
BRUCE PLEASE CALL 15 MIN BEFORE SO BRUCE CAN MEET WITH YOU; Phone #: ###-#### called contractor needs to provide access to light fixtures, he will reschedule when access is avalible 8/1/2002 4:23:53 PM
|
ELE02-02369
| Permanent Service | 8/1/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | PASS |
|
|
p/s o/h rec. ok
|
ELE02-02233
| Permanent Service | 8/1/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 08/01/2002 at 10:53:53. Contact: ###-####. called left message need load calculation for service 8/1/2002 6:11:02 PM
|
ELE99-02690
| Permanent Service | 8/1/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | PASS |
|
|
p/s o/h new ok
|
ELE02-02098
| Electrical Rough-In | 8/1/2002 | 8/1/2002 | 8/1/2002 12:00:00 AM | P | PART |
|
|
met with owner conference ok
|
ELE02-01950
| Final | 7/31/2002 | 8/1/2002 | 7/31/2002 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 07/31/2002 at 10:17:15. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 07/31/2002 at 10:36:54.
|