Inspections for the day of: Tuesday, August 1, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00524 FIR-Aging Inspection8/1/20068/1/20068/2/2006 1:39:22 PM DEFR
FIR06-00238 INSP-Sprinkler Rough-in/Hydro8/1/20068/1/20068/2/2006 11:35:05 AMPPART
UG hydrostatic test performed satisfactory.
FIR05-00632 INSP-Final Inspection7/31/20068/1/20068/2/2006 8:05:15 AMPDEFR
No time available to complete this inspection today, to be done 8/2 per agreement.
FIR06-00487 INSP-Sprinkler Rough-in8/1/20068/1/20068/2/2006 8:01:20 AMPDEFR
Inspection to be completed 8/2
BLD05-02838 FIRE-Final Inspection8/1/20068/1/20068/1/2006 4:19:33 PMPPASS
Fire life safety is acceptable, inspection passed.
BLD06-00863 FIRE-Final Inspection7/31/20068/1/20068/1/2006 3:48:20 PMAFAIL
The project related alarm permit must be inspected, approved and finaled prior to BLD life safety final.
FIR06-00430 INSP-Final Inspection7/31/20068/1/20068/1/2006 3:06:49 PMPPASS
Fire alarm work tested satisfactory, inspection passed.
FIR06-00210 INSP-Final Inspection7/31/20068/1/20068/1/2006 12:18:17 PMAFAIL
Inspectors test and main drain line not completed to allow final testing, need to attatch hyd. calc. sticker, provide locking means for the main control valves, one painted head under the stairs was replaced while on site.
FIR06-00210 INSP-Supply line flush7/31/20068/1/20068/1/2006 12:14:48 PMAPART
UG supply line flush performed satisfactory.
BLD06-00658 FIRE-Conference7/31/20068/1/20068/1/2006 11:00:28 AMADONE
Confrence with GC to discuss building addressing (number size, location), core and shell life safety requirements, and fire lane marking.
BLD06-01422 FIRE-Final Inspection7/31/20068/1/20068/1/2006 10:49:06 AMAPASS
Scope of work to install metal framing only for demising wall, existing smoke evac. system to be verified at future TI permit for occupancy inspections.
BLD06-02078 FIRE-Final Inspection7/31/20068/1/20068/1/2006 10:44:49 AMAFAIL
Need to provide current certification tag on the provided fire extinguisher and mount on the wall as discussed, provide approved door hardware at the restroom door, need to final fire sprinkler permit pending ceiling tile install, provide test of existing smoke evac system for verification of functionality.
FIR06-00547 INSP-Sprinkler Rough-in7/31/20068/1/20068/1/2006 10:41:34 AMAPART
OH fire sprinkler rough-in is good for cover at the drop ceiling areas, final pending ceiling tile and escutcheons.
FIR06-00546 INSP-Sprinkler Rough-in7/31/20068/1/20068/1/2006 9:41:49 AMAPART
OH inspection for the 3 heads in the RAD room only as marked on approved plans is acceptable.