ELE07-02633
| Electrical Rough-In | 8/1/2007 | 8/1/2007 | 8/1/2007 3:59:48 PM | P | PASS |
|
|
larry - cover Phone #: ###-#### u/g ok to cover
|
ELE07-02696
| Electrical Rough-In | 8/1/2007 | 8/1/2007 | 8/1/2007 3:25:28 PM | P | FAIL |
|
|
Contact Steve Berry with any problems or questions on the Rough in. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called, left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) recpts shall be installed such that no point along wall space is over 6' from an outlet, 314.20 in walls of combustible material, box shall be flush with finished surface
|
ELE07-02695
| Permanent Service | 8/1/2007 | 8/1/2007 | 8/1/2007 2:41:39 PM | P | FAIL |
|
|
brent; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called, left corr notice, nec 250.32(A) building supplied by feeder shall have grounding electrode system installed, BCC address shall be posted on bldg
|
ELE07-02693
| Temporary Service | 8/1/2007 | 8/1/2007 | 8/1/2007 2:00:55 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, left survey, nec 312.5 all conductors entering enclosure shall have abrasion protection, t/s u/g n ok
|
ELE07-01624
| Electrical Rough-In | 8/1/2007 | 8/1/2007 | 8/1/2007 1:24:46 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 8/1/2007 at 9:16:12 AM. Contact: ###-####. u/g for pole bases anop ok (north and west sides)
|
ELE07-01936
| Permanent Service | 7/31/2007 | 8/1/2007 | 8/1/2007 12:50:55 PM | P | PASS |
|
|
This is for permanent service, please call Ted with any questions. ###-#### Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa p/s u/g n ok
|
ELE07-02342
| Rough-In Permanent Service | 7/31/2007 | 8/1/2007 | 8/1/2007 11:09:14 AM | A | CANC |
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson met contr, said they wanted to cancel inspection
|
ELE07-02686
| Conference | 7/31/2007 | 8/1/2007 | 8/1/2007 10:55:40 AM | A | DONE |
|
|
kirk douglas-- ###-#### or ###-#### met owner, reviewed 1/14", free conductor, meter height, flush boxes, circuiting,
|
ELE07-02684
| Electrical Rough-In | 7/31/2007 | 8/1/2007 | 8/1/2007 10:23:06 AM | A | PASS |
|
|
Key in mail box on right of building ###-#### Internet Inspection Request from: Todd Holbrook called contr, ric ok walls and ceiling, service ltr
|
ELE07-01859
| Electrical Rough-In | 8/1/2007 | 8/1/2007 | 8/1/2007 9:46:05 AM | A | PASS |
|
|
Need rough inspection for basement living, bathroom, and laundry areas Phone #: ###-#### Internet Inspection Request from: Monty Adkinson ri ok for basement bath, laundry, living area
|
ELE07-02451
| Electrical Rough-In | 7/31/2007 | 8/1/2007 | 8/1/2007 9:12:20 AM | A | PART |
|
|
underground inspection. Please call Rick Sendra Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson south part u/g slab ok to pour
|
ELE07-02357
| Final | 7/31/2007 | 8/1/2007 | 8/1/2007 8:32:36 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman ok to final
|
ELE07-02546
| Temporary Service | 7/31/2007 | 8/1/2007 | 8/1/2007 7:58:03 AM | A | PASS |
|
|
dale - pls call for access; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr to put on cover, id ckts, id neut, t/s u/g n ok
|