ELE08-01508
| Rough-In Permanent Service | 8/1/2008 | 8/1/2008 | 8/1/2008 3:32:19 PM | P | CANC |
|
|
2nd floor panels ready for inspection Panel K L M N J Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig talked to contr about permits foe each meter
|
ELE08-02139
| Electrical Rough-In | 8/1/2008 | 8/1/2008 | 8/1/2008 2:42:24 PM | P | PASS |
|
|
Ric Phone #: ###-#### ok no esc
|
ELE08-01786
| Electrical Rough-In | 7/31/2008 | 8/1/2008 | 8/1/2008 1:51:43 PM | P | FAIL |
|
|
Bob- please call 1 hr prior to going Phone #: ###-#### corr., met contr NEC 110.2 equipment labeled but does not say what it is, and too many violations to note, some of the violations are box fill boxes not grounded, over 360 degrees of bends in raceways, needs 6" free length of conductors and strap within 12" of boxes for cables and flex note partial corr only this is for starbucks
|
ESC08-00432
| General Inspection | 8/1/2008 | 8/1/2008 | 8/1/2008 12:36:49 PM | P | PART |
|
|
site ok sprinkler system being installed
|
ELE08-01657
| Final | 8/1/2008 | 8/1/2008 | 8/1/2008 12:35:26 PM | P | PASS |
|
|
there is a key in the a/c disconnect, thanks. Internet Inspection Request from: Stephen Kren ok
|
ELE08-00665
| ELE-Aging Inspection | 8/1/2008 | 8/1/2008 | 8/1/2008 9:58:35 AM | | PART |
|
|
wsuc
|
ELE08-01131
| ELE-Aging Inspection | 8/1/2008 | 8/1/2008 | 8/1/2008 9:58:17 AM | | PART |
|
|
wsuc
|
ELE08-00626
| ELE-Aging Inspection | 8/1/2008 | 8/1/2008 | 8/1/2008 9:58:00 AM | | PART |
|
|
wsuc
|
ELE08-01585
| Final | 7/31/2008 | 8/1/2008 | 8/1/2008 9:12:08 AM | A | PASS |
|
|
Call Dan for access info. ###-#### Phone #: ###-#### Internet Inspection Request from: Dan Rohl called already finaled 07-16-08 by 432
|
ELE08-02135
| Temporary Service | 7/31/2008 | 8/1/2008 | 8/1/2008 9:05:14 AM | A | FAIL |
|
|
brian Note: late morning Phone #: ###-#### needs to post address job not ready service not grounded called no ESC
|
ELE08-01770
| Final | 7/31/2008 | 8/1/2008 | 8/1/2008 8:38:04 AM | A | CANC |
|
|
Please call before going so that I can meet you and let you into the building. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called contr will reschedule, needs to be attached to BLD permit, also called in wrong inspection request
|