Inspections for the day of: Friday, August 1, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00606 INSP-Sprinkler Rough-in7/31/20088/1/20088/1/2008 5:11:43 PMPFAIL
Noted locations on plan set at areas G and H in need of correction including overspaced heads at the weight room and stair B09, provide correct temp. heads at the three skylights, noted some heads still covered by foil due to painting in progress-some items repaired while on site. Still need area separation at the storage room C28, provide as-builts for changes at the electrical and mech. rooms, noted one blocked head at the riser room, no provision for forward flow testing at the riser has been provided. Area A deficiencies include prop storage calcs, as-builts for added upright protection, high temp head at the unit heater in the storage room, classroom A06 is not finished, angled soffit at the west side of the auditorium is obstructed.
FIR08-00255 INSP-Final Inspection7/29/20088/1/20088/1/2008 5:01:29 PMAPART
Manual pull stations and notification devices tested today per K. Roule, see plans for locations in need of adjustment.
FIR08-00482 INSP-Sprinkler Rough-in/Hydro7/31/20088/1/20088/1/2008 4:59:33 PMAPART
OH fire sprinkler system modifications are good for cover at the drop ceilings.
BLD08-01104 FIRE-Final Inspection7/31/20088/1/20088/1/2008 4:58:37 PMAFAIL
Provide approved hardware at two restrooms, two mechanical rooms and one office per plan notes, also need to post fire extinguishers no higher than 48" AFF.
FIR08-00324 INSP-Final Inspection7/31/20088/1/20088/1/2008 4:57:04 PMAPASS
Fire sprinkler work passed inspection, permit finaled.
BLD08-01553 FIRE-Final Inspection7/31/20088/1/20088/1/2008 10:12:04 AMAFAIL
Lacking fire sprinkler coverage at the stairway area between the upper and lower levels-sprinkler head is missing or has been obstructed by the drop ceiling. See item number 8 under general requirements listed on the permit notes regarding fire sprinklers. Notified the tenant that any modifications necessary must be performed by a licensed fire sprinkler contractor with a project related fire permit.