Inspections for the day of: Wednesday, August 1, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00818 FIRE-Final Inspection7/31/20128/1/20128/2/2012 3:32:22 PMPNR
James Phone #: ###-#### - life saety
FIR11-00575 INSP-Final Inspection8/1/20128/1/20128/2/2012 1:33:24 PMAPART
SD for elevator recall functions tested acceptable. Need to revise HD locations at the elevator machine room per NFPA 72 21.4.2.
FIR12-00099 INSP-Alarm Testing8/1/20128/1/20128/2/2012 1:23:54 PMAPART
System components tested today include vesda zones 8,9,10,11 and 12, added a/v at the SE fab exit, FP system #11 tamper and flow switch, verified outside bell function.
BLD12-00170 FIRE-Final Inspection7/31/20128/1/20128/2/2012 1:13:31 PMAPASS
Life safety inspection passed.
FIR12-00283 INSP-Final Inspection8/1/20128/1/20128/2/2012 1:11:31 PMAPASS
FIR12-00361 INSP-Final Inspection8/1/20128/1/20128/2/2012 1:11:12 PMAPASS
FIR12-00337 INSP-Final Inspection8/1/20128/1/20128/2/2012 1:10:46 PMAPASS
FIR12-00239 INSP-Final Inspection8/1/20128/1/20128/2/2012 1:10:23 PMAPASS
BLD12-01955 FIRE-Final Inspection7/30/20128/1/20128/1/2012 2:14:28 PMPPASS
Life safety okay pending satisfactory structural final inspection for verification of PFE and door hardware as discussed. Signature card not available at the time of site visit.
BLD12-00920 FIRE-Final Inspection7/31/20128/1/20128/1/2012 2:11:19 PMAFAIL
Correction items include; repair two EM lights, provide record of current annual certification for the existing fire sprinkler system, replace missing ceiling tile, post fire extinguisher as discussed.