Inspections for the day of: Thursday, August 1, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00289 INSP-Sprinkler Rough-in7/31/20138/1/20138/1/2013 3:43:22 PMPPASS
Piping can be covered. As-builts are needed showing the actual wall layout.
BLD13-01384 FIRE-Final Inspection7/31/20138/1/20138/1/2013 3:26:36 PMAPASS
life safety passed
FIR13-00314 INSP-Sprinkler Rough-in8/1/20138/1/20138/1/2013 2:58:46 PMPPART
Soffits as marked "ok" in red are ok to cover. But acouple issues need to be addressed which include the branchline supply piping to the heads in the east side soffit is shown on the plans as 1 1/4 but 1" has been installed (4 heads are being supplied). Also the supply piping for the sidewalls is shown to be 1 1/4" but only 1" has been installed (3 heads are being supplied). Soffits are ok to cover but piping needs to be installed as approved or plan modifications are needed for the pipe size changes.
FIR13-00335 INSP-Final Inspection7/30/20138/1/20138/1/2013 2:31:24 PMPFAIL
After I got to the job site I found that the suppression system had not been installed yet. zach and I discussed rescheduling when it gets installed. A tech from BRS believed that the micro switch is wired backwards any way.
BLD13-00415 FIRE-Final Inspection7/31/20138/1/20138/1/2013 2:04:27 PMPPASS
Life safety passed
FIR13-00351 INSP-Final Inspection7/29/20138/1/20138/1/2013 12:44:05 PMAPASS
Permit finaled
BLD13-01981 FIRE-Final Inspection7/31/20138/1/20138/1/2013 10:24:03 AMAPASS
Life safety passed. Grant will have an updated fire extinguisher in place prior to the building inspection.
BLD13-01758 FIRE-Final Inspection7/31/20138/1/20138/1/2013 9:36:39 AMAFAIL
Pendant heads are overspaced off from two of the classroom walls and are located too close together in two other locations. Also the exit sign in the classroom is burnt out.
FIR13-00326 INSP-Final Inspection7/31/20138/1/20138/1/2013 8:58:20 AMAPASS
permit finaled
FIR13-00330 INSP-Final Inspection7/31/20138/1/20138/1/2013 8:57:35 AMAPASS
Permit finaled