FIR13-00289
| INSP-Sprinkler Rough-in | 7/31/2013 | 8/1/2013 | 8/1/2013 3:43:22 PM | P | PASS |
|
|
Piping can be covered. As-builts are needed showing the actual wall layout.
|
BLD13-01384
| FIRE-Final Inspection | 7/31/2013 | 8/1/2013 | 8/1/2013 3:26:36 PM | A | PASS |
|
|
life safety passed
|
FIR13-00314
| INSP-Sprinkler Rough-in | 8/1/2013 | 8/1/2013 | 8/1/2013 2:58:46 PM | P | PART |
|
|
Soffits as marked "ok" in red are ok to cover. But acouple issues need to be addressed which include the branchline supply piping to the heads in the east side soffit is shown on the plans as 1 1/4 but 1" has been installed (4 heads are being supplied). Also the supply piping for the sidewalls is shown to be 1 1/4" but only 1" has been installed (3 heads are being supplied). Soffits are ok to cover but piping needs to be installed as approved or plan modifications are needed for the pipe size changes.
|
FIR13-00335
| INSP-Final Inspection | 7/30/2013 | 8/1/2013 | 8/1/2013 2:31:24 PM | P | FAIL |
|
|
After I got to the job site I found that the suppression system had not been installed yet. zach and I discussed rescheduling when it gets installed. A tech from BRS believed that the micro switch is wired backwards any way.
|
BLD13-00415
| FIRE-Final Inspection | 7/31/2013 | 8/1/2013 | 8/1/2013 2:04:27 PM | P | PASS |
|
|
Life safety passed
|
FIR13-00351
| INSP-Final Inspection | 7/29/2013 | 8/1/2013 | 8/1/2013 12:44:05 PM | A | PASS |
|
|
Permit finaled
|
BLD13-01981
| FIRE-Final Inspection | 7/31/2013 | 8/1/2013 | 8/1/2013 10:24:03 AM | A | PASS |
|
|
Life safety passed. Grant will have an updated fire extinguisher in place prior to the building inspection.
|
BLD13-01758
| FIRE-Final Inspection | 7/31/2013 | 8/1/2013 | 8/1/2013 9:36:39 AM | A | FAIL |
|
|
Pendant heads are overspaced off from two of the classroom walls and are located too close together in two other locations. Also the exit sign in the classroom is burnt out.
|
FIR13-00326
| INSP-Final Inspection | 7/31/2013 | 8/1/2013 | 8/1/2013 8:58:20 AM | A | PASS |
|
|
permit finaled
|
FIR13-00330
| INSP-Final Inspection | 7/31/2013 | 8/1/2013 | 8/1/2013 8:57:35 AM | A | PASS |
|
|
Permit finaled
|