Inspections for the day of: Friday, August 1, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02777 ELE-Aging Inspection8/1/20148/1/20148/6/2014 11:15:50 AM DONE
too busy
ELE12-01617 ELE-Aging Inspection8/1/20148/1/20148/4/2014 9:53:03 AM PASS
final ok
ELE14-00250 Final8/1/20148/1/20148/1/2014 1:59:45 PMPFAIL
Josh is contact Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.8 (A)(2) -garage outlets all need GFCI protection, 314.20-no more than 1/4" from finish surface to front edge of box(kitchen backsplash, 422.31- lockofss on cir. breakers for microwave and dbl. oven, loose kitchen counter recetacle, 2" strap on meter base conduit, dnst. laundry room has GFCI on GFCI from upst. bath
ELE14-01409 Electrical Rough-In8/1/20148/1/20148/1/2014 1:00:20 PMPFAIL
ceiling grid
for access call 86992600 Phone #: ###-#### Inspection requested via web by Lars Johnson 330.30(B)-secure MC cable within 6" of box, recessed can lights need seismic wire with identification, close up junction boxes
ELE14-02099 Temporary Service8/1/20148/1/20148/1/2014 12:38:16 PMPPASS
Joe Phone #: ###-#### t/s o/h n ok
ELE14-02034 Electrical Rough-In7/31/20148/1/20148/1/2014 11:53:09 AMAPART
partial r/i // Keith Phone #: ###-#### partial r/i ok see A2.0 sheets
ELE14-00951 Final8/1/20148/1/20148/1/2014 10:47:08 AMPFAIL
Victoria Phone #: ###-#### all outside conv. outlets need GFCI protection
ELE14-01852 Final8/1/20148/1/20148/1/2014 10:26:50 AMPPASS
final inspection
7/3 Poplar Glen Phone #: ###-#### Inspection requested via web by Rowdy Monroe FINAL OK
ELE14-02097 Temporary Service8/1/20148/1/20148/1/2014 9:45:04 AMAPASS
temp power pole Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok A;READY ENERGIZED AND METER SET
ELE14-02096 Temporary Service8/1/20148/1/20148/1/2014 9:36:23 AMAPASS
temp power pole Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s u/g n ok ALREADY ENERGIZED AND METER SET
GCE13-00191 GCE-Rough-In7/31/20148/1/20148/1/2014 9:27:23 AMAPASS
Rough-In for Office r/i ok remainder of lobby walls and ceilings and offices and kitchen ceiling only