FIR14-00412
| INSP-Final Inspection | 8/1/2014 | 8/1/2014 | 8/1/2014 6:17:11 PM | P | PASS |
|
|
Scope of work completed. Fire sprinkler permit passed final walkthrough.
|
FIR14-00316
| INSP-Sprinkler Rough-in | 7/31/2014 | 8/1/2014 | 8/1/2014 6:07:47 PM | A | PART |
|
|
Rough-in inspection completed for the west classroom wing as noted on plans. Missing hangers at classroom 123, lateral brace at the corridor, fire caulk at classroom 126- all corrected while on site. Need to revise spacing issues in classroom #8 room 125. Attic access room and library 130A are incomplete at this time. Remainder of classrooms and corridor are okay for cover per dated annotations.
|
FIR14-00456
| INSP-Sprinkler Rough-in | 7/31/2014 | 8/1/2014 | 8/1/2014 5:59:26 PM | A | NH |
|
|
Jeremy Phone #: ###-####
|
FIR14-00281
| INSP-Final Inspection | 7/24/2014 | 8/1/2014 | 8/1/2014 11:31:02 AM | A | FAIL |
|
|
Completed initial walkthrough. Items noted include; lower manual pull stations per note #18 and plan comments, relocate SD at a storage room 1st floor, remove non-functional existing smoke detectors at various locations 1st floor, adjust visual coverage at two rooms in the dispatch center, SD in mens and womens restrooms 1st floor to be located a min. of 3' from HVAC diffusers, missing SD at the storage closet below the stairs 1st floor, add SD at the 2nd floor mens restroom, revise detector coverage at the storage closet 2nd floor, post points map at the panel per review note #24. Knox box per note # 25 is not installed.
|
FIR14-00103
| INSP-Sprinkler Rough-in/Hydro | 7/31/2014 | 8/1/2014 | 8/1/2014 11:19:35 AM | A | PART |
|
|
Remainder of UG fire supply line to the point of connection at the property line is approved for bury.
|