Inspections for the day of: Friday, August 1, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00412 INSP-Final Inspection8/1/20148/1/20148/1/2014 6:17:11 PMPPASS
Scope of work completed. Fire sprinkler permit passed final walkthrough.
FIR14-00316 INSP-Sprinkler Rough-in7/31/20148/1/20148/1/2014 6:07:47 PMAPART
Rough-in inspection completed for the west classroom wing as noted on plans. Missing hangers at classroom 123, lateral brace at the corridor, fire caulk at classroom 126- all corrected while on site. Need to revise spacing issues in classroom #8 room 125. Attic access room and library 130A are incomplete at this time. Remainder of classrooms and corridor are okay for cover per dated annotations.
FIR14-00456 INSP-Sprinkler Rough-in7/31/20148/1/20148/1/2014 5:59:26 PMANH
Jeremy Phone #: ###-####
FIR14-00281 INSP-Final Inspection7/24/20148/1/20148/1/2014 11:31:02 AMAFAIL
Completed initial walkthrough. Items noted include; lower manual pull stations per note #18 and plan comments, relocate SD at a storage room 1st floor, remove non-functional existing smoke detectors at various locations 1st floor, adjust visual coverage at two rooms in the dispatch center, SD in mens and womens restrooms 1st floor to be located a min. of 3' from HVAC diffusers, missing SD at the storage closet below the stairs 1st floor, add SD at the 2nd floor mens restroom, revise detector coverage at the storage closet 2nd floor, post points map at the panel per review note #24. Knox box per note # 25 is not installed.
FIR14-00103 INSP-Sprinkler Rough-in/Hydro7/31/20148/1/20148/1/2014 11:19:35 AMAPART
Remainder of UG fire supply line to the point of connection at the property line is approved for bury.