Inspections for the day of: Friday, August 1, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00443 INSP-Sprinkler Rough-in/Hydro8/1/20148/1/20148/1/2014 3:23:44 PMPPASS
Hydro test of the FDC supply piping passed
FIR14-00548 INSP-Final Inspection8/1/20148/1/20148/1/2014 3:09:31 PMPCANC
To be rescheduled when the project related fire alarm interconnection is complete and ready to be tested.
FIR13-00514 INSP-Final Inspection7/31/20148/1/20148/1/2014 2:49:48 PMPFAIL
Owner wanted us to reschedule due to the crowds. I noted that 14 guage wire was installed not 12 guage as per the approved plans. Also the 75cd ceiling mounted horn/strobes need to have reduced spacing due to the height at which they have been installed. Also the 110cd ceiling moiunt strobe at teh very end of the tenant space is overspaced off of the wall in the picnic table area. And the NAC panel has been relocated to a different location in the building. No actual testing was performed.
FIR14-00228 INSP-Sprinkler Rough-in7/31/20148/1/20148/1/2014 2:15:45 PMPPASS
See the city approved plans for additional classrooms where the piping is approved for cover.
FIR14-00399 INSP-Sprinkler Rough-in8/1/20148/1/20148/1/2014 12:05:00 PMPPASS
ug rough to cover passed
FIR14-00221 INSP-Final Inspection8/1/20148/1/20148/1/2014 11:35:31 AMPPASS
Permit finaled
FIR13-00612 INSP-Sprinkler Rough-in/Hydro7/31/20148/1/20148/1/2014 10:27:55 AMPCANC
Robert is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR14-00285 INSP-Final Inspection7/31/20148/1/20148/1/2014 10:19:38 AMACANC
We were told there is a final and the alarm called in already. Werent sure
if its am or pm. Please call Mark 1/2 hr prior to inspection. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR14-00443 INSP-Sprinkler Rough-in/Hydro7/31/20148/1/20148/1/2014 10:17:26 AMAFAIL
Visable drop in guage pressure of 5psi
FIR14-00280 INSP-Sprinkler Rough-in7/31/20148/1/20148/1/2014 9:33:52 AMAPART
1st floor Quail Court Rough In passed and piping can be covered. One problem is there has been non-rated wood installed above the ceiling assembly that will need to be addressed prior to a final sign off. I spoke to Clarence and John about this problem.
BLD14-01057 FIRE-Supply Line Hydro7/31/20148/1/20148/1/2014 9:06:50 AMACANC
Need the project related fire alarm permits finaled, fire extinguishers tagged and exit signs repaired. No life safety inspection was performed.
FIR14-00450 INSP-Final Inspection7/31/20148/1/20148/1/2014 9:05:00 AMACANC
Could not perform testing since Alarmco was not scheduled for the dialer inspection. I did however verify correct placement of the a/v's