Inspections for the day of: Wednesday, August 1, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02296 Electrical Rough-In8/1/20188/1/20188/1/2018 2:29:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Grid rough in ok cover
ELE17-02862 Electrical Rough-In8/1/20188/1/20188/1/2018 1:57:30 PMPPASS
Drop ceilings hallway 4th floor Phone #: ###-#### Inspection requested via web by Tom Betty
Corridor and storage room drop lids rough in ok cover.
ELE18-01470 Final8/1/20188/1/20188/1/2018 1:50:09 PMPPASS
Please Call Corey when onsite Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
ELE18-02291 Final8/1/20188/1/20188/1/2018 12:52:28 PMPPASS
Contact: Josh Mangum Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
ELE18-02909 Electrical Rough-In8/1/20188/1/20188/1/2018 11:07:33 AMAPASS
Call Travis for access at the # above Phone #: ###-#### Inspection requested via web by David Green
Kitchen remodel. Discussed if counter space to right of micowave 12" or wider a receptacle will be required to serve this counter space. Rough in ok cover
ELE18-02904 Final7/31/20188/1/20188/1/2018 10:27:38 AMAPASS
Wired the lights in the hall and store. Wired the POS Phone #: ###-#### Inspection requested via web by Greg Idsinga Final ok
ELE18-02904 Electrical Rough-In8/1/20188/1/20188/1/2018 10:09:08 AMPPASS
Wired the lights in the hall and store. Wired the POS Phone #: ###-#### Inspection requested via web by Greg Idsinga
Changed lighting in store and corridor, added receptacles to POS. Rough in ok.
ELE18-02672 Final7/31/20188/1/20188/1/2018 9:50:54 AMAFAIL
Call Lance for access to space if not open
208.703.2035 Phone #: ###-#### Inspection requested via web by David Feller

BCC 4-05-32- No code violation shall be retained.

300.11- Misc cables shall be supported independant of grid.
314.25- All boxes containing a splice shall have covers. 3 open boxes near front of space. All device covers off for painting.
ELE18-02878 Temporary Service7/31/20188/1/20188/1/2018 9:23:40 AMAPASS
Call Mikel with any questions. Phone #: ###-#### Inspection requested via web by Bonnie Page
t/s u/g n ok
ELE18-02908 Temporary Service7/31/20188/1/20188/1/2018 9:07:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey
t/s u/g n ok
ELE18-01618 Final7/30/20188/1/20188/1/2018 8:56:03 AMAPASS
Install new message board into existing pole sign. All Primary power to remain as is Phone #: ###-#### Inspection requested via web by Ken Olsen
Final ok
ELE18-01618 Electrical Rough-In7/30/20188/1/20188/1/2018 8:55:36 AMAPASS
Install new message board into existing pole sign. All Primary power to remain as is Phone #: ###-#### Inspection requested via web by Ken Olsen
Disconnecting means confirmed
MIS18-00286 ELE-Conference7/30/20188/1/20187/31/2018 12:11:03 PMADONE
Check on work being performed without permit. Elc work being done without a permit per Bill Phone #: ###-####
Called owner of 3107 W. Crescent Rim and apologized for mixed up address, 3107 original address listed. Work covered ELE18-02894. Drywalled shower and 1 side of closet only. Informed no 1 siding.
ELE18-01550 Electrical Rough-In8/1/20188/1/20187/31/2018 12:00:00 AMAPASS
per inspection from voided permit ELE18-02867