Inspections for the day of: Tuesday, August 10, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-01054 FIRE-Sprinkler Rough-in8/9/20048/10/20048/10/2004 12:00:00 AMAFAIL
sprinkler pendants in restrooms 1-2 and 2-1 are spaced too close. Less than 6'. Sprinkler pendants in restroom 1-1 are ok 8/10/2004 11:02:59 AM
BLD04-01054 FIRE-Final Inspection8/9/20048/10/20048/10/2004 12:00:00 AMAFAIL
Life safety items are ok in restrooms 1-1, 1-2 and 2-1 but pendant sprinkers are spaced too close in restrooms 1-2 and 2-1. The city approved plans do not show the garbage shutes that have been built. I told the contractor to provide this information to the plan reviewer to see if resubmittals will be required for the building plans. 8/10/2004 11:06:04 AM
BLD04-00495 FIRE-Final Inspection8/9/20048/10/20048/10/2004 12:00:00 AMAPART
A temporary occupancy was given until the exit discharge lighting has been installed and the door hardware has been installed on the west half of the building. The east half of the building is ok to occupy as all life safety items other than discharge lighting is OK. 8/10/2004 11:01:29 AM
BLD04-00983 FIRE-Final Inspection8/9/20048/10/20048/10/2004 12:00:00 AMAFAIL
The fire extinguishers are mounted higher than 48". All other items are ok 8/10/2004 2:17:54 PM
BLD04-00783 FIRE-Final Inspection8/10/20048/10/20048/10/2004 12:00:00 AMPPASS
Fire life safety finaled 8/10/2004 2:18:23 PM
FIR04-00377 INSP-Final Inspection8/10/20048/10/20048/10/2004 12:00:00 AMPPASS
fire alarm finaled 8/10/2004 4:02:11 PM
BLD04-00865 FIRE-Final Inspection8/10/20048/10/20048/10/2004 12:00:00 AMPPASS
fire life safety finaled 8/10/2004 4:02:35 PM
BLD03-01726 FIRE-Final Inspection8/10/20048/10/20048/10/2004 12:00:00 AMPPASS
Fire life safety finaled