ELE05-02105
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 5:17:50 PM | P | PASS |
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
ELE05-02222
| Final | 8/9/2005 | 8/10/2005 | 8/10/2005 4:50:16 PM | P | FAIL |
|
|
final inspect for branch panel & hot tub circuit; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH cor. posted called hot tub wired to canadian standards shall replace or have it tested by testing lab for US standards, 680.26(C) use min. #8 solid for bonding, 680.22(A)(3) outlet shall be no closer than 10FT no further than 20ft
|
ELE05-02868
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 3:48:59 PM | P | CANC |
|
|
before 3pm please//duane; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called duane
|
ELE05-01875
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 3:41:50 PM | P | PASS |
|
|
final is for service only
|
ELE05-02642
| Permanent Service | 8/10/2005 | 8/10/2005 | 8/10/2005 3:09:08 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s u/g new ok
|
ELE05-02792
| Electrical Rough-In | 8/10/2005 | 8/10/2005 | 8/10/2005 2:08:27 PM | P | PART |
|
|
wall cover inspection, please contact Gary (# given is pager), thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters new freezer wall ok
|
ELE05-02099
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 1:51:27 PM | P | PASS |
|
|
Final for room #14. Please call Chris at ###-#### with any questions.; Phone #: ###-#### Internet Inspection Request from: todd hall ok no card at site
|
ELE05-00996
| Final | 8/9/2005 | 8/10/2005 | 8/10/2005 1:20:33 PM | P | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted met contractor 410.8 install fixtures as code noted states disable wiring where fixtures are not allowed,250.148 grd metal boxes, need access to jtub equip,408.4 label panel 314.23 secure box in kit
|
ELE05-02909
| Electrical Rough-In | 8/9/2005 | 8/10/2005 | 8/10/2005 12:14:24 PM | A | PART |
|
|
cover inspection//mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa new wall bed rm
|
ELE05-02894
| Electrical Rough-In | 8/8/2005 | 8/10/2005 | 8/10/2005 11:49:48 AM | A | PART |
|
|
Phone #: ###-#### x Internet Inspection Request from: John Campbell r/i rest rm ok
|
ELE04-03015
| Electrical Rough-In | 8/9/2005 | 8/10/2005 | 8/10/2005 11:26:34 AM | A | NR |
|
|
larry Note: pool - pool light compound; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called not ready
|
ELE05-02894
| Permanent Service | 8/10/2005 | 8/10/2005 | 8/10/2005 12:00:00 AM | A | PASS |
|
|
p/s o/h rec. ok
|