Inspections for the day of: Wednesday, August 10, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01660 Final8/10/20058/10/20058/10/2005 4:22:58 PMPNH
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left card
ELE05-01659 Final8/10/20058/10/20058/10/2005 4:22:11 PMPNH
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left card.
ELE05-00284 Final8/9/20058/10/20058/10/2005 4:13:51 PMPPASS
ready for final, please contact Steve, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters signed occ card, ok to final
ELE05-02923 Electrical Rough-In8/10/20058/10/20058/10/2005 3:06:37 PMPFAIL
conduit trench inspection please///shawn ###-#### told owner. 300.5 cnd to be 18" deep, called elect
ELE05-02759 Permanent Service8/9/20058/10/20058/10/2005 3:00:53 PMPPASS
please call prior to inspection so he can meet ya there in the mid afternoon please////tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s o/h exst ok
ELE05-02058 Final8/10/20058/10/20058/10/2005 2:31:19 PMPPASS
Scheduled by a contractor via Hello! on 8/10/2005 at 9:34:31 AM. Contact: ###-####. called contr, left message, left survey, 406.4(B) recpt shall be rigidly mounted, 406.5 recpt faceplate shall seat against the mounting surface
ELE05-02020 Final8/10/20058/10/20058/10/2005 12:29:55 PMPFAIL
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 408.4 panel schedule shall identify specific circuits completely, 210.52 (C)(2)island shall have recpt, 440.4(A) a/c breaker shall be sized per nameplate on ac, 110.3(A) lights shall work in stairs and up stairs bath
ELE05-02910 Electrical Rough-In8/9/20058/10/20058/10/2005 11:35:37 AMAPASS
###-#### - don Note: please call 1/2 hr prior ric ok
ELE05-02918 Final8/9/20058/10/20058/10/2005 9:34:06 AMAFAIL
andy ###-#### called, left message, left corr notice, 300.5, and BCC conduit shall be min 6" deep and exposed for inspection, 342.42(A) connectors shall be made up tight, 342.30(A) imc shall be supported within 3" of box and conduit termination, 408.4 circuit directory shall be evident for use.
ELE05-02451 Electrical Rough-In8/9/20058/10/20058/10/2005 8:50:54 AMAPART
ceiling cover inspection, please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to cover center portions except where fixtures not in yet
ELE05-02917 Final8/9/20058/10/20058/10/2005 8:28:22 AMAPASS
andy ###-#### called contr, left survey, ok to final
ELE05-02915 Rough-In Permanent Service8/9/20058/10/20058/10/2005 8:13:20 AMAFAIL
clyde ###-#### called, left message, left corr notice, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 110.12(C) nm cable jacketing shall not be cut,314.23(C)(1) framing members shall be adequately fastened to each other, 314.23(B) boxes shall be rigidly supported, note to contr on job id sticker has wrong permit number on it