ELE05-01660
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 4:22:58 PM | P | NH |
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left card
|
ELE05-01659
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 4:22:11 PM | P | NH |
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left card.
|
ELE05-00284
| Final | 8/9/2005 | 8/10/2005 | 8/10/2005 4:13:51 PM | P | PASS |
|
|
ready for final, please contact Steve, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters signed occ card, ok to final
|
ELE05-02923
| Electrical Rough-In | 8/10/2005 | 8/10/2005 | 8/10/2005 3:06:37 PM | P | FAIL |
|
|
conduit trench inspection please///shawn ###-#### told owner. 300.5 cnd to be 18" deep, called elect
|
ELE05-02759
| Permanent Service | 8/9/2005 | 8/10/2005 | 8/10/2005 3:00:53 PM | P | PASS |
|
|
please call prior to inspection so he can meet ya there in the mid afternoon please////tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s o/h exst ok
|
ELE05-02058
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 2:31:19 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/10/2005 at 9:34:31 AM. Contact: ###-####. called contr, left message, left survey, 406.4(B) recpt shall be rigidly mounted, 406.5 recpt faceplate shall seat against the mounting surface
|
ELE05-02020
| Final | 8/10/2005 | 8/10/2005 | 8/10/2005 12:29:55 PM | P | FAIL |
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 408.4 panel schedule shall identify specific circuits completely, 210.52 (C)(2)island shall have recpt, 440.4(A) a/c breaker shall be sized per nameplate on ac, 110.3(A) lights shall work in stairs and up stairs bath
|
ELE05-02910
| Electrical Rough-In | 8/9/2005 | 8/10/2005 | 8/10/2005 11:35:37 AM | A | PASS |
|
|
###-#### - don Note: please call 1/2 hr prior ric ok
|
ELE05-02918
| Final | 8/9/2005 | 8/10/2005 | 8/10/2005 9:34:06 AM | A | FAIL |
|
|
andy ###-#### called, left message, left corr notice, 300.5, and BCC conduit shall be min 6" deep and exposed for inspection, 342.42(A) connectors shall be made up tight, 342.30(A) imc shall be supported within 3" of box and conduit termination, 408.4 circuit directory shall be evident for use.
|
ELE05-02451
| Electrical Rough-In | 8/9/2005 | 8/10/2005 | 8/10/2005 8:50:54 AM | A | PART |
|
|
ceiling cover inspection, please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to cover center portions except where fixtures not in yet
|
ELE05-02917
| Final | 8/9/2005 | 8/10/2005 | 8/10/2005 8:28:22 AM | A | PASS |
|
|
andy ###-#### called contr, left survey, ok to final
|
ELE05-02915
| Rough-In Permanent Service | 8/9/2005 | 8/10/2005 | 8/10/2005 8:13:20 AM | A | FAIL |
|
|
clyde ###-#### called, left message, left corr notice, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 110.12(C) nm cable jacketing shall not be cut,314.23(C)(1) framing members shall be adequately fastened to each other, 314.23(B) boxes shall be rigidly supported, note to contr on job id sticker has wrong permit number on it
|